{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0DA25-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0DA25-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0DA25-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0DA25-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-0DA25-ZW96 motor protection circuit breaker, size S00, CLASS 10, 0.32 A, 100 kA breaking capacity, spring-type terminals, with transverse auxiliary switches 1 NO + 1 NC.","salesMarkdown":"It carries a CLASS 10 trip characteristic, meaning it will trip within 10 seconds at 7.2× the thermal setting — the standard for protecting standard induction motors during start-up without nuisance tripping on normal acceleration. Rated operational current is 0.32 A, with an adjustable thermal overload release range that covers the motor full-load current. The magnetic short-circuit release responds at 4.2 A, providing instantaneous protection against bolted faults. Breaking capacity is a flat 100 kA across the full voltage range from 240 V through 690 V AC, so it clears high-fault-current events without cascading upstream — a key spec for panels with high available fault current. The breaker ships with factory-installed transverse auxiliary switches (1 NO + 1 NC) for remote status indication or interlocking. Snap-on mounting onto 35 mm DIN rail per EN 60715 is standard for the S00 frame. ## Fit and integration notes The S00 frame shares the same 45 mm width and 97 mm depth as the standard 3RV2011 base variants. It snaps onto 35 mm DIN rail and occupies the same panel footprint as the screw-terminal versions (3RV2011-0AA10) or ring-lug version (3RV2011-0AA40). The spring-terminal variant (this one) differs only in the connection method — no change to mounting, spacing, or auxiliary wiring layout. The handle provides a visible break position for lockout/tagout. Side-by-side mounting is zero-gap on both sides, saving rail space in dense panels.","metaTitle":"Siemens 3RV2011-0DA25-ZW96 SIRIUS Motor Circuit Breaker, 0.3","metaDescription":"Siemens SIRIUS 3RV2011-0DA25-ZW96 motor protection circuit breaker, 0.32 A, CLASS 10, 100 kA breaking capacity, spring-type terminals. Active lifecycle, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Trip Class":"CLASS 10","Rated Value":"20 ... 690 V","lifecycle_stage":"current","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 500 V rated value":"100 kA","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Substance Prohibitance (Date)":"10/01/2009","Operational Current Rated Value":"0.32 A","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"4.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/427f8a84728ea65a2d757a7d02896f80.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1357086&mlfb=3RV2011-0DA25-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0DA25-ZW96/alternatives.json"},"ai":{"faq":[{"question":"What is the trip class and what does it mean?","answer":"CLASS 10 means the overload relay will trip within 10 seconds at 7.2× the current setting. This is the standard trip class for protecting standard three-phase induction motors during direct-on-line starting."},{"question":"What is the breaking capacity of this breaker?","answer":"100 kA at all AC voltages from 240 V through 690 V. This flat high-breaking-capacity rating means it can be used in high-fault-current panels without needing upstream current-limiting fuses."},{"question":"Will 3RV2011-0DA25-ZW96 drop into a panel specified for 3RV2011-0BA20?","answer":"Yes, same S00 frame, same 45 mm width, same DIN-rail mounting. The only difference is the connection method: this one uses spring terminals, while the 0BA20 uses screw terminals. Panel cutouts and auxiliary wiring layout are identical."},{"question":"Where can I buy 3RV2011-0DA25-ZW96?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0DA25-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0DA25-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}