{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0EA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0EA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0EA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0EA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, size S00, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw-type terminals, 45 mm wide, for 35 mm DIN rail.","salesMarkdown":"It carries a Trip Class 10, meaning it trips within 10 seconds at 7.2× the thermal setting current — fast enough to protect standard induction motors during a locked-rotor event. The 100 kA breaking capacity at 400 V AC (and up to 690 V AC) means it can safely interrupt high fault currents without upstream fuses in most panel designs, simplifying coordination. The 45 mm width and 97 mm depth fit standard S00 footprint — drops into existing panels without re-drilling. Requires 50 mm clearance above and below and 30 mm at the sides for heat dissipation and wiring access. Any mounting position allowed. ## Electrical ratings and protection Rated insulation voltage 20 to 690 V. Main circuit uses screw-type terminals, accepting 2× 0.75–2.5 mm² or 2× 4 mm² solid/stranded. Maximum switching frequency at AC-3 duty is 15 cycles per hour. Operating temperature range -20 to +60 °C; storage/transport -50 to +80 °C.","metaTitle":"Siemens 3RV2011-0EA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2011-0EA10 SIRIUS motor protection circuit breaker, size S00, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw terminals, DIN rail mount. Sourced to order agai","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2011-0EA10","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for motor protection, CLASS 10 A-release 0.28...0.4 A N-release 5.2 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.4 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.4 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.4 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.4 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.4 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"5.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.28 ... 0.4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$27.94","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bbdacad776acef1f6c55e9e0c1ef2306.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=366916&mlfb=3RV2011-0EA10"},"ai":{"faq":[{"question":"How do I get pricing and availability for 3RV2011-0EA10?","answer":"Submit an RFQ through this listing. The part is sourced to order; current pricing and lead time are confirmed at quote time."},{"question":"What is the closest functional second-source for 3RV2011-0EA10?","answer":"The 3RV2011-0AA10 is a close functional peer — same size S00, same Trip Class 10, same 100 kA breaking capacity, same DIN rail footprint. The -0EA10 differs in its specific thermal setting range (not listed in evidence), so verify the overload setting matches your motor FLA before substituting."},{"question":"Will 3RV2011-0EA10 drop into a panel specified for 3RV2011-0AA10?","answer":"Yes — both are size S00, same 45 mm width, same DIN rail mounting, same screw terminal pattern. No rewiring or panel modification needed for the swap."},{"question":"What compliance documentation does Siemens provide for 3RV2011-0EA10?","answer":"Siemens typically provides RoHS, REACH, and CE declarations for SIRIUS circuit breakers. UL and IEC certifications are standard for this series. Specific document numbers are available on request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0EA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0EA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}