{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0EA40","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0EA40","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0EA40","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0EA40","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-0EA40, size S00 motor protection circuit breaker, 45 mm wide, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"It mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715, with a compact 45 mm width that saves panel space. Trip Class 10 means it trips within 10 seconds at 7.2× the thermal setting — standard for general-purpose motor starting on pumps, fans, and conveyors where the inrush doesn't demand a slower class. ## Breaking Capacity & Selectivity Rated 100 kA at 400 V AC and at 690 V AC, this breaker handles high fault currents without upstream fuses in most panel designs — useful when coordinating with a transformer or a main breaker that can't clear a bolted fault alone. ## Mounting & Panel Fit Mounting position is any. The 45 mm width and 97 mm depth make it a direct fit in standard S00-size slots. Clearance: 50 mm upwards, 50 mm downwards, 30 mm to the side — no extra space needed front or back. Main circuit connections use ring cable lugs; screwdriver shaft diameter 5–6 mm, tip size 2 / Pozidriv 2.","metaTitle":"Siemens 3RV2011-0EA40 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2011-0EA40 SIRIUS motor protection circuit breaker, size S00, 45 mm wide, 100 kA breaking capacity at 400 V AC. Trip Class 10, phase failure detection. Currently in prod","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.4 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.4 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"Ring cable lug connection","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"size 2 and Pozidriv 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.4 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.4 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.4 A","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"ring terminal lug connection","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","For Main Contacts For Ring Cable Lug":"0.8 ... 1.2 N·m","Surge Voltage Resistance Rated Value":"6 kV","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Number Of Poles For Main Current Circuit":"3","For Auxiliary Contacts For Ring Cable Lug":"1.2 ... 0.8 N·m","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Outer Diameter Of The Usable Ring Cable Lug Maximum":"7.5 mm","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"5.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.28 ... 0.4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c67e4f727d5476fde20c062b39a2e84d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=24168&mlfb=3RV2011-0EA40","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0EA40/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the 3RV2011-0EA40 at 400 V?","answer":"100 kA at 400 V AC and at 690 V AC, giving high fault-current withstand for motor branch circuits."},{"question":"What is the trip class of this breaker?","answer":"Trip Class 10 — trips within 10 seconds at 7.2× the thermal setting, suitable for standard motor starting."},{"question":"Where can I buy the 3RV2011-0EA40 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Does the 3RV2011-0EA40 have phase failure detection?","answer":"Yes, phase failure detection is built in — a lost phase on the line side will trip the breaker to protect the motor."},{"question":"What compliance documentation is available for the 3RV2011-0EA40?","answer":"As a Siemens SIRIUS product, it is designed to meet IEC and UL standards. Specific RoHS, REACH, and UL documentation is provided by the manufacturer and can be supplied with the order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0EA40","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0EA40 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}