{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0FA15-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0FA15-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0FA15-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0FA15-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2011-0FA15-ZW97, Trip Class 10, 100 kA at 400 V, screw terminals, 45 mm width, DIN rail mount.","salesMarkdown":"It combines a circuit breaker and overload relay in one device, providing short-circuit and overload protection for motors up to 0.1 kW at 230 V. Built-in phase failure detection protects the motor from single-phasing, which is a common cause of winding burnout on three-phase lines. No ground fault detection — that's handled separately if required. Width is 45 mm — a standard 2-module footprint that fits most panel layouts. Terminal screws for main contacts are M3, accepting 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded copper. Clearance distances: 50 mm upwards and downwards, 30 mm at the sides, 0 mm forwards and backwards — the forward/backward zero means it can be stacked flush against the panel door or backplane, saving space.","metaTitle":"Siemens 3RV2011-0FA15-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2011-0FA15-ZW97 SIRIUS motor protection circuit breaker, Trip Class 10, 100 kA at 400 V, phase failure detection. Currently in production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 690 V":"gL/gG 4 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.5 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.5 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.5 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.5 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.5 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"1.8 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"6.5 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.35 ... 0.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b15c3575022279decabcc497200a1fed.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=437861&mlfb=3RV2011-0FA15-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0FA15-ZW97/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3RV2011-0FA15-ZW97?","answer":"Trip Class 10, breaking capacity 100 kA at 400 V, phase failure detection, motor protection design for 0.1 kW at 230 V. Width 45 mm, depth 97 mm, DIN rail mount."},{"question":"Will 3RV2011-0FA15-ZW97 drop into a panel specified around 3RV2011-0AA10?","answer":"The 3RV2011-0FA15-ZW97 shares the same 45 mm width and DIN rail mounting as the 3RV2011-0AA10, so it fits the same panel footprint and rail. Terminal sizes and wiring are identical. The difference is in the trip class and breaking capacity — verify the protection settings match your motor."},{"question":"How do I get pricing and availability for 3RV2011-0FA15-ZW97?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0FA15-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0FA15-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}