{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0GA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0GA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0GA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0GA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-0GA10 motor protection circuit breaker, size S00, 45 mm wide, 100 kA breaking capacity at 400 V AC, Trip Class 10, screw terminals, snap-on DIN rail mount.","salesMarkdown":"It's designed to protect motor branch circuits against overload, short circuit, and phase failure — the three faults that take out a motor on a conveyor zone or pump station. Breaking capacity is 100 kA at 400 V AC and 500 V AC, and the same 100 kA at 690 V AC. The 45 mm width is the S00 standard — one 45 mm slot on the rail. Any mounting position is allowed, which helps when you're packing breakers into a tight enclosure. Clearance requirements: 50 mm above and below, 30 mm to the sides, 0 mm forward and backward. That's the space you need for arc quenching and terminal access — plan for it in the gland plate layout. Terminals are M3 screw-type for the main circuit, accepting 2× (0.75 to 2.5 mm²) or 2× 4 mm² solid or stranded. Screwdriver shaft diameter 5 to 6 mm — a standard Pozidriv #2 or flathead will fit. ## Environmental and lifecycle The storage range is wider because the breaker isn't carrying current — it's the thermal-magnetic trip elements that limit the operating range, not the housing. Lifecycle status is current production. It's a line item you can quote to order against an RFQ without worrying about obsolescence.","metaTitle":"Siemens SIRIUS 3RV2011-0GA10 Motor Protection Circuit Breake","metaDescription":"Siemens SIRIUS 3RV2011-0GA10 motor protection circuit breaker, size S00, 100 kA SCCR at 400 V AC, Trip Class 10, phase failure detection, 45 mm wide, current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 690 V":"gL/gG 6 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.63 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.63 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.63 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.63 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.63 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"8.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.45 ... 0.63 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$83.57 – $152.38","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=484271&mlfb=3RV2011-0GA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0GA10/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions for panel layout?","answer":"Width is 45 mm, depth is 97 mm, height is 97 mm. Clearance: 50 mm above and below, 30 mm to the sides, 0 mm forward and backward."},{"question":"What breaking capacity does it have at 400 V?","answer":"100 kA at 400 V AC, and the same 100 kA at 500 V AC and 690 V AC. That's a high interrupting rating for a size S00 breaker."},{"question":"Does it detect phase failure?","answer":"Yes, phase failure detection is built in. It will trip if one phase is lost, protecting the motor from single-phasing."},{"question":"What trip class is it?","answer":"Trip Class 10, meaning it trips within 10 seconds at 7.2× the thermal setting. This is standard for protecting standard induction motors during starting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0GA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0GA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}