{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0GA15-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0GA15-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0GA15-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0GA15-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-0GA15-ZW97 motor protection circuit breaker, 100 kA at 400 V, Trip Class 10, screw-type terminals, 45 mm width, 97 mm depth, DIN rail mount.","salesMarkdown":"## Motor protection circuit breaker — SIRIUS 3RV2011-0GA15-ZW97 Rated short-circuit breaking capacity reaches 100 kA at 400 V, 500 V, and 690 V, and also at 240 V — that is a high-fault rating for a 45 mm wide device, so it can be used as the main branch protector in a distribution panel without needing a separate upstream fuse for SCCR coordination, provided the available fault current stays under that level. ## DIN rail integration and clearances This is typical for SIRIUS 3RV2 breakers and matches the footprint of the standard 3RV2011 family, meaning a panel originally wired for a 3RV2011-0AA10 or 3RV2011-0BA20 will accept this unit without re-drilling or re-routing the DIN rail. Screw-type terminals on the main current circuit accept solid or stranded conductors: 2 × (0.5 … 1.5 mm²) or 2 × (0.75 … 2.5 mm²). The terminal screws are M3 size. ## Ratings and so-what The auxiliary contacts (for signalling the breaker state) are rated 1 A at 24 V, 0.5 A at 120/125/230 V, and 0.15 A at 60 V. The main circuit short-circuit protection uses gL/gG fuses rated 6 A at 690 V. The maximum switching frequency in AC-3 duty (motor starting) is 15 operations per hour; the same limit applies for AC-3e duty. Power rating at 230 V is 0.1 kW. For motor protection, the thermal setting range must be selected to match the motor full-load current; the breaker's own continuous rating must be at least that value.","metaTitle":"Siemens 3RV2011-0GA15-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV2011-0GA15-ZW97 motor protection circuit breaker, 100 kA at 400 V, Trip Class 10, DIN rail mount, current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Trip Class":"CLASS 10","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/48dce2b4f712dbca11985de4f623729b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=200998&mlfb=3RV2011-0GA15-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0GA15-ZW97/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0GA15-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0GA15-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}