{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0GA20-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0GA20-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0GA20-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0GA20-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2011-0GA20-ZW97, frame size S00, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw and snap-on DIN rail mounting, spring-loaded terminals.","salesMarkdown":"Rated Trip Class 10, it clears overloads within 10 seconds at 7.2× setting current — the standard for protecting standard induction motors against locked-rotor conditions without nuisance tripping during normal starts. Breaking capacity reaches 100 kA at 400 V AC and 690 V AC, providing high fault-current interruption capability that supports selective coordination downstream without cascading upstream breakers. Dimensions are 45 mm wide, 106 mm high, and 97 mm deep, with required clearances of 50 mm above and below, 30 mm to the sides, and zero forward or backward clearance needed. The compact footprint leaves room for adjacent devices in a crowded enclosure. Main circuit connections use spring-loaded terminals, accepting 2x (0.5 to 4 mm²) solid or stranded wire. A 3 mm screwdriver shaft is specified for the terminal screws. Mounting position is any, giving flexibility for horizontal or vertical busbar arrangements in the panel.","metaTitle":"Siemens 3RV2011-0GA20-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2011-0GA20-ZW97 SIRIUS motor protection circuit breaker, frame size S00, Trip Class 10, 100 kA breaking capacity at 400 V, screw and snap-on DIN rail mounting. Available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Upwards":"50 mm","Forwards":"0 mm","at 690 V":"gL/gG 6 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","Mounting Position":"any","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.63 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.63 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"spring-loaded terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.63 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.63 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.63 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (20 ... 12)","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"8.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.45 ... 0.63 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=479538&mlfb=3RV2011-0GA20-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0GA20-ZW97/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV2011-0GA20-ZW97 and how do I get a price?","answer":"It is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 3RV2011-0GA20-ZW97 drop into a panel that was specified around 3RV2011-0BA20 without rewiring?","answer":"Both share the same S00 frame size and DIN rail mounting, so the physical footprint and rail clip are identical. Terminal type and ratings differ — verify the load current and trip class against the existing application before swapping."},{"question":"What compliance documentation does this brand provide for 3RV2011-0GA20-ZW97?","answer":"As a Siemens SIRIUS product, it carries CE marking and is designed to IEC/EN 60947 standards. RoHS and REACH declarations are available from Siemens documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0GA20-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0GA20-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}