{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0GA25-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0GA25-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0GA25-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0GA25-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, 3RV2011-0GA25-ZX95, Trip Class 10, 100 kA breaking capacity at 400 V AC, phase failure detection, spring-loaded terminals, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"## Motor protection breaker, 100 kA class Its Trip Class 10 characteristic means it will trip within 10 seconds at 7.2× the thermal setting — standard protection for standard induction motors, not for high-inertia loads that need Class 20 or longer. Rated breaking capacity hits 100 kA at 400 V AC (and also at 240 V, 500 V, 690 V per the spec table). On a three-phase motor, if one phase drops, the breaker opens before single-phasing cooks the winding. This is a standard expectation on motor-rated breakers, but worth confirming if your BOM spec requires it — some economy breakers omit it. Any mounting position is allowed. Spring-loaded terminals accept 2× (0.5 to 2.5 mm²) solid or stranded copper. Clearance dimensions: 50 mm upwards and downwards, 30 mm at the side, 0 mm forwards and backwards. That 0 mm forward/backward clearance means the breaker can be mounted flush against a panel wall or backplane — no breathing gap needed at the front or rear. Auxiliary contact ratings are given for several control voltages: 1 A at 24 V, 0.5 A at 120 V, 0.5 A at 125 V, 0.5 A at 230 V, and 0.15 A at 60 V. These are the switching capacities for the built-in auxiliary contacts — useful when sizing the control transformer or verifying the PLC output can drive the breaker's aux circuit. ## Environmental range The temperature compensation is specified over the same -20 to +60 °C operating window, meaning the thermal trip curve stays within tolerance across that span without manual adjustment.","metaTitle":"Siemens 3RV2011-0GA25-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2011-0GA25-ZX95 SIRIUS motor protection circuit breaker. Trip Class 10, 100 kA breaking capacity at 400 V, phase failure detection, spring-loaded terminals. Sourced to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Trip Class":"CLASS 10","Product Status":"Active","Temp Operating Max":"60 °C","Temp Operating Min":"-20 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2ac654a66b099a642363520885df0ee1.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=604019&mlfb=3RV2011-0GA25-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0GA25-ZX95/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0GA25-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0GA25-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}