{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0HA10-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0HA10-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0HA10-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0HA10-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, size S00, Trip Class 10, 100 kA breaking capacity at 400 V, phase failure detection, screw-type terminals, 3RV2011-0HA10-ZX95.","salesMarkdown":"The 3RV2011-0HA10-ZX95: Mounts via screw fixing or snap-on onto a 35 mm DIN rail per DIN EN 60715. The 45 mm width and 97 mm depth fit standard S00 panel layouts. Terminal capacity accepts 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm², with M3 screw terminals for the main current circuit.","metaTitle":"Siemens 3RV2011-0HA10-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2011-0HA10-ZX95 SIRIUS motor protection circuit breaker, size S00, Trip Class 10, 100 kA breaking capacity at 400 V, phase failure detection. Current production. Quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 690 V":"gL/gG 6 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.8 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.8 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"0.8 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.8 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.8 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"10 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.55 ... 0.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05559c4a468182a2e35546fa130c4686.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=267399&mlfb=3RV2011-0HA10-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0HA10-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV2011-0HA10-ZX95 at 400 V?","answer":"It has a 100 kA breaking capacity at 400 V AC, which means it can safely interrupt fault currents up to that level without upstream devices needing to clear the fault."},{"question":"What is the Trip Class of this circuit breaker?","answer":"It is Trip Class 10, meaning it will trip within 10 seconds at 600% of the thermal setting, protecting the motor during start-up."},{"question":"Does 3RV2011-0HA10-ZX95 detect phase failure?","answer":"Yes, it includes phase failure detection, which prevents single-phasing damage to the motor."},{"question":"How do I get pricing and availability for 3RV2011-0HA10-ZX95?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ to confirm current pricing and availability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0HA10-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0HA10-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}