{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0JA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0JA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0JA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0JA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-0JA10 motor-protection circuit breaker, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw terminals, 45 mm wide, DIN-rail mount.","salesMarkdown":"The Siemens 3RV2011-0JA10 is a SIRIUS motor-protection circuit breaker designed to protect motors against overload and short circuits. It is Trip Class 10, meaning it will trip within 10 seconds at 7.2× the thermal setting — fast enough for standard induction motors starting under load. The 100 kA breaking capacity at 400 V AC means it can interrupt a fault current up to that level without upstream fuses or breakers needing to clear the fault; this rating holds across 240 V through 690 V (, –), so it handles high-fault-capacity panels without cascading coordination issues. The 45 mm width occupies a single modular slot — fits standard panel layouts without oversizing the enclosure. Screw-type terminals on the main circuit accept 2× (0.75…2.5 mm²) solid or stranded, or 2× 4 mm². Ambient operating range –20…+60 °C; storage –50…+80 °C.","metaTitle":"Siemens 3RV2011-0JA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2011-0JA10 SIRIUS motor-protection circuit breaker, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw terminals, DIN-rail mount. Active lifecycle.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2011-0JA10","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 500 V":"gL/gG 10 A","at 690 V":"gL/gG 10 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for motor protection, CLASS 10 A-release 0.7...1 A N-release 13 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.2 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"1 A","at 500 V rated value":"100 kA","at 600 V rated value":"1 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 575/600 V rated value":"0.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"1 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"1 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"13 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$90.21 – $200.56","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2a1bf89d0fb9c8cd3b00b33355fcf9a7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=229314&mlfb=3RV2011-0JA10"},"ai":{"faq":[{"question":"What is the breaking capacity of the 3RV2011-0JA10?","answer":"100 kA at 240 V, 400 V, 500 V, and 690 V AC (, –). This is the short-circuit breaking capacity per IEC 60947-2, meaning the breaker can safely interrupt a fault up to that level without damage."},{"question":"What is the Trip Class of the 3RV2011-0JA10?","answer":"Trip Class 10 — the thermal overload element trips within 10 seconds at 7.2× the set current. This is the standard class for general-purpose motor protection."},{"question":"Does the 3RV2011-0JA10 detect phase failure?","answer":"Yes, phase failure detection is built in. Ground fault detection is not included."},{"question":"What are the mounting dimensions of the 3RV2011-0JA10?","answer":"Width 45 mm, height 97 mm, depth 97 mm (–). Mounts on 35 mm DIN rail per DIN EN 60715."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0JA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0JA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}