{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-0JA25-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-0JA25-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-0JA25-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0JA25-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011 motor protection circuit breaker, 3RV2011-0JA25-ZW96, Trip Class 10, 100 kA breaking capacity at 400 V, spring-loaded terminals, snap-on DIN rail.","salesMarkdown":"It combines a circuit breaker and overload relay in one unit, with Trip Class 10 protection. It also includes phase failure detection, so if one leg drops out, the breaker opens before the motor single-phases and cooks the winding. ## Mounting and terminals Any mounting position is allowed, which gives flexibility in tight cabinets. The main circuit uses spring-loaded terminals — no screwdriver needed for the power wires, just strip and push. Accepts 2 x 0.5 to 2.5 mm² solid or stranded. That 45 mm width is a single module on the rail — leaves room for other breakers or contactors in the row. ## Environmental and aux ratings Storage and transport range extends from -50 to +80 °C. Auxiliary contact ratings: 1 A at 24 V, 0.5 A at 120/125/230 V, 0.15 A at 60 V. Rated operational voltage spans 20 to 690 V AC.","metaTitle":"Siemens 3RV2011-0JA25-ZW96 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2011-0JA25-ZW96 SIRIUS motor protection circuit breaker, Trip Class 10, 100 kA breaking capacity at 400 V, spring-loaded terminals, snap-on DIN rail. Sourced to order ag","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 500 V":"gL/gG 10 A","at 690 V":"gL/gG 10 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.2 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"1 A","at 500 V rated value":"100 kA","at 600 V rated value":"1 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"spring-loaded terminals","Temperature Compensation":"-20 ... +60 °C","at 575/600 V rated value":"0.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"1 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1 A","at AWG cables for main contacts":"2x (20 ... 12)","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"spring-loaded terminals","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 14)","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","Finely Stranded Without Core End Processing":"2x (0.5 ... 1.5 mm²)","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"13 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=622680&mlfb=3RV2011-0JA25-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-0JA25-ZW96/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RV2011-0JA25-ZW96?","answer":"The depth is 97 mm."},{"question":"What is the width of 3RV2011-0JA25-ZW96?","answer":"The width is 45 mm."},{"question":"Will 3RV2011-0JA25-ZW96 drop into a panel specified for 3RV2011-0BA20 without rewiring?","answer":"Both are SIRIUS 3RV2011 motor protection circuit breakers with the same 45 mm width and DIN rail mounting, so mechanical fit should be identical. However, terminal type and auxiliary contact ratings may differ — verify the wiring diagram against your existing panel before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-0JA25-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-0JA25-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}