{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1AA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1AA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1AA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1AA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-1AA10 motor protection circuit breaker, Class 10, 100 kA SCCR at 400 V, screw-type terminals, 45 mm width.","salesMarkdown":"It is Class 10 trip, detects phase failure, and has no ground-fault detection. ## Short-circuit ratings and selectivity That kind of SCCR headroom means you can usually coordinate it downstream of a larger molded-case or air circuit breaker without worrying about the motor starter becoming the weak link in a fault. Width is 45 mm, depth 97 mm, height 97 mm. ## Terminals and wiring Main circuit connections are screw-type terminals sized for M3 screws. Accepts up to 2x 4 mm² solid or stranded, or 2x (0.75 to 2.5 mm²) — plenty for the motor leads on a fractional-to-small integral-horsepower motor. No special torque specs in the evidence, but standard M3 screw torque around 0.5–0.6 Nm will get you a reliable connection. The screw terminals are a plus for panel builders who prefer them over spring-clamp for high-vibration environments.","metaTitle":"Siemens 3RV2011-1AA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2011-1AA10 SIRIUS motor protection circuit breaker, Class 10 trip, 100 kA SCCR at 400 V, screw terminals, DIN rail mount. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2011-1AA10","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 500 V":"gL/gG 20 A","at 690 V":"gL/gG 16 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for motor protection, CLASS 10 A-release 1.1...1.6 A N-release 21 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"1.6 A","at 500 V rated value":"100 kA","at 600 V rated value":"1.6 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 460/480 V rated value":"1 hp","at 575/600 V rated value":"0.8 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"1.6 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"1.6 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1.6 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"21 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.1 ... 1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$82.99 – $187.66","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9ffb31eb5a2092682b736fdc1d2142e4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=115492&mlfb=3RV2011-1AA10"},"ai":{"faq":[{"question":"What clearance is needed around the 3RV2011-1AA10 in a panel?","answer":"50 mm above and below, 30 mm to the sides, zero clearance in front or back. Mounting position is any orientation."},{"question":"Does this breaker detect phase failure?","answer":"Yes, phase failure detection is included. Ground fault detection is not available on this model."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1AA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1AA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}