{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1AA10-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1AA10-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1AA10-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1AA10-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2011-1AA10-ZW96, Class 10 trip, 100 kA breaking capacity at 400 V AC, 45 mm wide, screw and snap-on DIN rail mount.","salesMarkdown":"## What this breaker does in the panel The breaking capacity is 100 kA at 400 V AC (also 100 kA at 240 V, 500 V, and 690 V), which means it can safely interrupt very high fault currents without upstream fuses needing to clear first. That 100 kA rating covers most industrial service-entrance and sub-distribution scenarios. ## Motor sizing and trip coordination This breaker carries a motor rating of 1 hp at 460/480 V and 0.8 hp at 575/600 V. At 230 V it is rated 0.1 hp. The thermal overload setting range is not listed in the spec excerpt, but the 20...690 V rated value covers the full low-voltage motor range. For a 1 hp 480 V motor, this breaker provides coordinated protection without needing a separate overload relay in most panel designs. The main circuit terminals are M3 screw-type, accepting 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm². Clearance: 50 mm upwards and downwards, 30 mm to the side, 0 mm forwards and backwards — so it can be packed tight against a backplane or adjacent devices as long as vertical airflow and wiring space are respected.","metaTitle":"Siemens 3RV2011-1AA10-ZW96 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV2011-1AA10-ZW96 motor protection circuit breaker. Class 10 trip, 100 kA breaking capacity at 400 V, 45 mm wide. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 500 V":"gL/gG 20 A","at 690 V":"gL/gG 16 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"1.6 A","at 500 V rated value":"100 kA","at 600 V rated value":"1.6 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","at 460/480 V rated value":"1 hp","at 575/600 V rated value":"0.8 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"1.6 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1.6 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"21 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.1 ... 1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d023a7eff3cebc0a8b988b3bd06dcad1.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=39093&mlfb=3RV2011-1AA10-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1AA10-ZW96/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"100 kA at 400 V AC, 240 V AC, 500 V AC, and 690 V AC — sufficient for most industrial fault-current scenarios without needing upstream fuses to assist."},{"question":"Will 3RV2011-1AA10-ZW96 drop into a panel specified for 3RV2011-0AA10?","answer":"Both share the same 45 mm width and DIN rail mounting, so mechanical fit is identical. The -ZW96 variant carries a different thermal setting range or special code; verify the overload setting matches your motor FLA before committing the BOM line."},{"question":"Where can I buy 3RV2011-1AA10-ZW96?","answer":"This part is sourced to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and delivery window."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1AA10-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1AA10-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}