{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1BA15-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1BA15-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1BA15-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1BA15-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2011-1BA15-ZW97, Class 10 trip, 100 kA breaking capacity at 400 V, 45 mm wide, screw and snap-on DIN rail mount.","salesMarkdown":"## Motor protection circuit breaker for panel integration Rated short-circuit breaking capacity reaches 100 kA at 240 V, 400 V, and 500 V, and 10 kA at 690 V. The gL/gG fuse-limit ratings (25 A at 400/500 V, 20 A at 690 V) define the maximum backup fuse that preserves selectivity. If you are coordinating a panel with gG fuses upstream, those values tell you the fuse size that will let the breaker trip first on a downstream fault. Mounting position is any, but the clearance requirements are specific: 50 mm upwards and downwards, 30 mm at the side, and 0 mm forwards and backwards. That 50 mm vertical clearance is critical for heat dissipation from the bimetal trip element — cramming it into a tight wireway without that gap will cause premature thermal tripping. Main circuit terminals accept 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded copper, terminated with M3 screws. The auxiliary contact block (rated 1 A at 24 V, 0.5 A at 120/230 V) shares the same screw-type terminal format — consistent with the main circuit termination.","metaTitle":"Siemens 3RV2011-1BA15-ZW97 SIRIUS Motor Protection CB, 100 k","metaDescription":"Siemens 3RV2011-1BA15-ZW97 SIRIUS motor protection circuit breaker, Class 10 trip, 100 kA SCCR at 400 V, 45 mm wide, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 400 V":"gL/gG 25 A","at 500 V":"gL/gG 25 A","at 690 V":"gL/gG 20 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.13 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"2 A","at 500 V rated value":"100 kA","at 600 V rated value":"2 A","at 690 V rated value":"10 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","at 460/480 V rated value":"1 hp","at 575/600 V rated value":"1 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"10 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"2 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"2 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"26 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.4 ... 2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/18f1f7d5a63699f107ccb62f3607d5b6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=104390&mlfb=3RV2011-1BA15-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1BA15-ZW97/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RV2011-1BA15-ZW97?","answer":"The depth is 97 mm, with a height of 97 mm and width of 45 mm. These dimensions include the breaker body only — add clearance for wiring and auxiliary contact blocks."},{"question":"What compliance documentation does Siemens provide for this breaker?","answer":"As a SIRIUS motor protection circuit breaker, it carries the standard Siemens declarations for RoHS, REACH, UL, and IEC compliance. Specific certificate numbers and declaration documents are available on request at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1BA15-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1BA15-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}