{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1DA15-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1DA15-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1DA15-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1DA15-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-1DA15-ZX95 motor protection circuit breaker, Class 10, 100 kA SCCR at 400 V, phase failure detection, screw and snap-on 35 mm DIN rail mount, 45 mm wide.","salesMarkdown":"## Motor protection circuit breaker, SIRIUS series Rated for a supply voltage range of 20 to 690 V, it carries a 100 kA short-circuit breaking capacity at 240 V, 400 V, and 500 V, dropping to 10 kA at 690 V. The fuse backup ratings are specified: gL/gG 25 A at 400 V and 690 V, gL/gG 32 A at 500 V. The 45 mm width (three 15 mm modules) fits standard panel layout grids. Any mounting position is permitted, with minimum clearances of 50 mm upward and downward, 30 mm to the side, and zero forward/backward clearance required. Terminal capacity accepts 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded wire; main contact screws are M3.","metaTitle":"Siemens 3RV2011-1DA15-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV2011-1DA15-ZX95 motor protection circuit breaker, Class 10 trip, 100 kA SCCR at 400 V, phase failure detection, DIN rail mount. Current production. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 400 V":"gL/gG 25 A","at 500 V":"gL/gG 32 A","at 690 V":"gL/gG 25 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.25 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"3.2 A","at 500 V rated value":"100 kA","at 600 V rated value":"3.2 A","at 690 V rated value":"10 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.1 hp","at 200/208 V rated value":"0.5 hp","at 220/230 V rated value":"0.75 hp","at 460/480 V rated value":"2 hp","at 575/600 V rated value":"2 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"10 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"3.2 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"03/01/2017","at AC-3e at 400 V rated value":"3.2 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"3.2 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"2.4 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"42 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.2 ... 3.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fb93d6094cfe0d88c465e5f3a555acd1.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=308300&mlfb=3RV2011-1DA15-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1DA15-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source for 3RV2011-1DA15-ZX95?","answer":"The 3RV1011-0GA10 and 3RV1011-1HA10 are the closest peers in the SIRIUS 3RV10 series. The 3RV2011-1DA15-ZX95 is a 3RV2 generation device; the 3RV10 series shares the same form factor and DIN rail footprint, but verify the specific thermal setting range and auxiliary contact configuration for your application — the 3RV2 series has a different internal trip mechanism and may not be a pin-for-pin drop-in without reviewing the wiring diagram."},{"question":"Where can I buy 3RV2011-1DA15-ZX95?","answer":"This part is sourced and quoted to order against an RFQ through independent industrial automation distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1DA15-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1DA15-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}