{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1DA25","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1DA25","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1DA25","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1DA25","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2011-1DA25, CLASS 10 trip, 100 kA at 400 V, screw and snap-on 35 mm DIN rail, spring-loaded terminals.","salesMarkdown":"## Motor protection circuit breaker for the line side Rated operating voltage spans 20 to 690 V, and the interrupting capacity reaches 100 kA at 400 V and 500 V, dropping to 10 kA at 690 V — a figure that governs selectivity with the upstream feeder breaker in a motor control centre. Spring-loaded terminals accept 2x 0.5 to 2.5 mm² solid or stranded conductors. The 3RV2011-1DA25 occupies a 45 mm wide footprint on the DIN rail, with a depth of 97 mm and height of 106 mm — that leaves room for a contactor alongside in the same 45 mm slot, provided the side clearance of 30 mm is observed for heat dissipation. ## Auxiliary contact ratings and switching frequency The integrated auxiliary contact is rated 1 A at 24 V, 0.5 A at 120/125/230 V, and 0.15 A at 60 V — these are the switching capacities for the signal circuit, not the main power path, so they suit a PLC input or a contactor coil, provided the coil inrush does not exceed the 1 A at 24 V limit. Maximum switching frequency in AC-3 duty (motor starting) is 15 operations per hour, which matches the typical jogging rate for a conveyor or pump start — not a high-cycle servo axis.","metaTitle":"Siemens 3RV2011-1DA25 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2011-1DA25 SIRIUS motor protection circuit breaker, CLASS 10 trip, 100 kA at 400 V, screw/snap-on DIN rail. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 400 V":"gL/gG 25 A","at 500 V":"gL/gG 32 A","at 690 V":"gL/gG 25 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.25 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"3.2 A","at 500 V rated value":"100 kA","at 600 V rated value":"3.2 A","at 690 V rated value":"10 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"0.1 hp","at 200/208 V rated value":"0.5 hp","at 220/230 V rated value":"0.75 hp","at 460/480 V rated value":"2 hp","at 575/600 V rated value":"2 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"10 kA","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"3.2 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"3.2 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"3.2 A","at AWG cables for main contacts":"2x (20 ... 12)","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"spring-loaded terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 14)","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","Finely Stranded Without Core End Processing":"2x (0.5 ... 1.5 mm²)","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"42 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.2 ... 3.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$40.64","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2dec71788242b47aa175f1e6de5e2723.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=499601&mlfb=3RV2011-1DA25","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1DA25/alternatives.json"},"ai":{"faq":[{"question":"What is 3RV2011-1DA25's depth?","answer":"The depth is 97 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1DA25","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1DA25 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}