{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1DA25-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1DA25-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1DA25-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1DA25-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-1DA25-ZW96 motor protection circuit breaker, Class 10, 100 kA breaking capacity at 400 V, screw and snap-on 35 mm DIN rail, spring-loaded terminals.","salesMarkdown":"That 100 kA breaking capacity at 400 V (and at 240 V, 500 V) tells you it can sit upstream of a fault without needing a backup fuse for most industrial distribution; at 690 V it still holds 10 kA, enough for 690 V line-side applications. Dimensions are 45 mm wide, 106 mm tall, 97 mm deep. Clearance: 50 mm upward and downward, 30 mm at the side, zero forward and backward. That's SCCR-level capability for most industrial panels. The 15 operations per hour maximum at AC-3 duty (and AC-3e) sets the switching pace — fine for a motor start/stop cycle, not for rapid reversing or jogging duty. Spring-loaded terminals accept 2x (0.5 to 2.5 mm²) solid or stranded — typical for control wiring up to 14 AWG. No ferrule needed, but stranded wire benefits from one for consistent insertion. Mounts in any position — vertical, horizontal, upside-down — the breaker's thermal-magnetic trip curve doesn't care about orientation. Side clearance of 30 mm to adjacent devices is the minimum for heat dissipation. Spring terminals on the main circuit mean no screwdriver calibration — strip to 8-10 mm, push in. The auxiliary contact block (if added) shares the same spring-clamp interface. Verify the wire ferrule size against the 2.5 mm² maximum before terminating.","metaTitle":"Siemens 3RV2011-1DA25-ZW96 SIRIUS Motor Protection Breaker,","metaDescription":"Siemens 3RV2011-1DA25-ZW96 SIRIUS motor protection circuit breaker, Class 10, 100 kA breaking capacity at 400 V, spring terminals, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 400 V":"gL/gG 25 A","at 500 V":"gL/gG 32 A","at 690 V":"gL/gG 25 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.25 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"3.2 A","at 500 V rated value":"100 kA","at 600 V rated value":"3.2 A","at 690 V rated value":"10 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"0.1 hp","at 200/208 V rated value":"0.5 hp","at 220/230 V rated value":"0.75 hp","at 460/480 V rated value":"2 hp","at 575/600 V rated value":"2 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"10 kA","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"3.2 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"3.2 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"3.2 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (20 ... 12)","For Auxiliary And Control Circuit":"spring-loaded terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","for AWG cables for auxiliary contacts":"2x (20 ... 14)","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","Finely Stranded Without Core End Processing":"2x (0.5 ... 1.5 mm²)","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"42 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.2 ... 3.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2a49890eabad72b5904abae4fd7f9b27.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=806718&mlfb=3RV2011-1DA25-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1DA25-ZW96/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV2011-1DA25-ZW96 drop into a panel specified for 3RV2021-1FA15 without rewiring?","answer":"Both are SIRIUS motor protection breakers with the same 45 mm width and DIN-rail snap-on mounting, so the physical footprint and rail position are identical. The 3RV2021-1FA15 is a higher-current variant; verify the thermal setting range matches your motor FLA before swapping — the terminal type and clearance requirements are the same."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1DA25-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1DA25-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}