{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1EA10-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1EA10-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1EA10-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1EA10-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, Size S00, 3RV2011-1EA10-0BA0, Trip Class 10, 100 kA breaking capacity at 400 V AC, gG 32 A at 400 V, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"Its Trip Class 10 means it trips within 10 seconds at 7.2× the thermal setting — the standard for standard-duty motor starting, not for high-inertia loads that need Class 20. The breaker detects phase failure, so a lost phase on the line side will drop the motor offline before single-phasing damages the winding. ## Panel Fit — Size S00 Footprint The 3RV2011-1EA10-0BA0 occupies the S00 frame: 45 mm wide, 97 mm deep, 97 mm tall. Clearance requirements are 50 mm upward and downward, 30 mm to the side, and zero forward or backward. That means it can be stacked tight front-to-back in a multi-row enclosure, but needs breathing room above and below for arc-quenching and terminal access. Terminals are screw-type for the main current circuit, accepting 2×(0.75…2.5 mm²) solid or stranded, or 2×4 mm². Screwdriver shaft diameter 5 to 6 mm, Pozidriv size 2 tip. No ground-fault detection built in — if GF protection is needed, add an external module or use a different SIRIUS variant.","metaTitle":"Siemens 3RV2011-1EA10-0BA0 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2011-1EA10-0BA0 SIRIUS motor protection circuit breaker, Size S00, Trip Class 10, 100 kA at 400 V AC, gG 32 A at 400 V. Phase failure detection. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 400 V":"gG 32 A","at 500 V":"gG 32 A","at 690 V":"gG 25 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-50 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.8 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 500 V rated value":"100 kA","at 690 V rated value":"4 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"500","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"4 A","Of Auxiliary Contacts Typical":"500","Substance Prohibitance (Date)":"10/01/2009","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"4 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"500","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"52 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.8 ... 4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/28f458f34a94be286d4d264f397c4184.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=124034&mlfb=3RV2011-1EA10-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1EA10-0BA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3RV2011-1EA10-0BA0 and get a price?","answer":"Sourced to order against an RFQ through independent distribution. Submit a request with your quantity; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of the 3RV2011-1EA10-0BA0 at 400 V?","answer":"100 kA at 400 V AC. At 690 V AC it is 4 kA. The backup fuse recommendation is gG 32 A at 400 V and below, gG 25 A at 690 V."},{"question":"Will the 3RV2011-1EA10-0BA0 drop into a panel specified for the 3RV2011-0AA10?","answer":"Both are Size S00 with the same 45 mm width and 97 mm depth, so the mechanical footprint and DIN-rail clip are identical. The difference is in the internal trip range and accessories — verify the overload setting range of the -0AA10 against the -1EA10 before swapping. The mounting holes and terminal layout match."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1EA10-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1EA10-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}