{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1EA10-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1EA10-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1EA10-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1EA10-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2011-1EA10-ZX95, Trip Class 10, 100 kA SCCR at 400 V, phase failure detection, screw and snap-on 35 mm DIN rail mounting.","salesMarkdown":"Its Trip Class 10 means it will trip within 10 seconds at 7.2× the thermal setting current, which is the standard for standard-duty motor starting — it handles normal acceleration without nuisance tripping but clears a stalled rotor fast enough to protect the winding insulation. Rated for 100 kA short-circuit breaking capacity at 240 V, 400 V, and 500 V, this breaker can be installed on high-fault-current panels without needing upstream current-limiting fuses in most industrial distributions. At 690 V the SCCR drops to 4 kA, so on 690 V systems verify the available fault current stays below that. No ground fault detection on this variant. The 45 mm width (three 15 mm modules) fits standard enclosure rail spacing. Any mounting position is allowed, which simplifies layout in crowded panels. Dimensions are 97 mm high × 45 mm wide × 97 mm deep. Clearance requirements: 50 mm above and below, 30 mm to the sides, 0 mm forward and backward — so it can be packed tightly front-to-back against a backplate or busbar.","metaTitle":"Siemens 3RV2011-1EA10-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2011-1EA10-ZX95 SIRIUS motor protection circuit breaker, Trip Class 10, 100 kA SCCR at 400 V, phase failure detection. Current lifecycle stage. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 400 V":"gL/gG 32 A","at 500 V":"gL/gG 32 A","at 690 V":"gL/gG 25 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.33 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"4 A","at 500 V rated value":"100 kA","at 600 V rated value":"4 A","at 690 V rated value":"4 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.13 hp","at 200/208 V rated value":"0.8 hp","at 220/230 V rated value":"0.75 hp","at 460/480 V rated value":"2 hp","at 575/600 V rated value":"3 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"4 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"4 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"4 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 ... 14), 2x 12","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"52 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.8 ... 4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/643c36a97d07cabf22010660c0ffe9b5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=508461&mlfb=3RV2011-1EA10-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1EA10-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the short-circuit breaking capacity of 3RV2011-1EA10-ZX95?","answer":"100 kA at 240 V, 400 V, and 500 V; 4 kA at 690 V. This covers most industrial panel fault levels at the common voltages."},{"question":"What are the mounting dimensions and clearances for 3RV2011-1EA10-ZX95?","answer":"97 mm high × 45 mm wide × 97 mm deep. Requires 50 mm clearance above and below, 30 mm to the sides, and 0 mm forward and backward."},{"question":"Does 3RV2011-1EA10-ZX95 include phase failure protection?","answer":"Yes, phase failure detection is built in. Ground fault detection is not included on this variant."},{"question":"Where can I buy 3RV2011-1EA10-ZX95 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1EA10-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1EA10-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}