{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1EA15-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1EA15-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1EA15-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1EA15-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor-protective circuit breaker, 3RV2011-1EA15-ZW97, Trip Class 10, 100 kA breaking capacity at 400 V AC, 45 mm wide, screw and snap-on DIN rail mounting.","salesMarkdown":"It carries a 100 kA breaking capacity at 400 V and 500 V, and 4 kA at 690 V, so it handles high fault currents on a 400 V distribution bus without cascading upstream. Auxiliary contact ratings span 1 A at 24 V down to 0.15 A at 60 V, covering PLC input or contactor coil circuits. The 100 kA SCCR at 400 V (and 500 V) means it safely interrupts a bolted fault at that level; at 690 V the breaking capacity drops to 4 kA, so verify the available fault current if the circuit runs at 690 V. The 20–690 V rated operating range covers low-voltage motor control panels globally. Maximum switching frequency is 15 operations per hour in AC-3 duty (motor starting), which suits conveyor, pump, and fan cycles but not rapid jogging or reversing service. The 45 mm width (3 module spaces) matches standard enclosure fill-factor calculations. Main contact terminals accept 2× (0.5 to 1.5 mm²) solid or stranded, or 2× (0.75 to 2.5 mm²) with ferrules; screw terminals are M3. Clearance to adjacent devices: 50 mm upward and downward, 30 mm to the side. No ground fault detection built in, so downstream RCD or separate ground-fault module is needed for personnel protection.","metaTitle":"Siemens 3RV2011-1EA15-ZW97 SIRIUS Motor Protection CB, Class","metaDescription":"Siemens SIRIUS 3RV2011-1EA15-ZW97 motor-protective circuit breaker. Trip Class 10, 100 kA breaking at 400 V, 45 mm wide, DIN rail. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 400 V":"gL/gG 32 A","at 500 V":"gL/gG 32 A","at 690 V":"gL/gG 25 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.33 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"4 A","at 500 V rated value":"100 kA","at 600 V rated value":"4 A","at 690 V rated value":"4 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.13 hp","at 200/208 V rated value":"0.8 hp","at 220/230 V rated value":"0.75 hp","at 460/480 V rated value":"2 hp","at 575/600 V rated value":"3 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"4 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"4 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"4 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"2.4 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"52 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.8 ... 4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7025777f5913c3d8e59177e38b20402c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=401270&mlfb=3RV2011-1EA15-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1EA15-ZW97/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RV2011-1EA15-ZW97?","answer":"Submit an RFQ through this listing. Pricing and availability are confirmed at quote time through our independent distribution channels — no stock or price figures are published here."},{"question":"What is the closest functional alternative to 3RV2011-1EA15-ZW97?","answer":"The 3RV1011-1HA10 is a Siemens SIRIUS motor-protective breaker in the same 45 mm footprint and Trip Class 10, but its breaking capacity and auxiliary contact configuration may differ. Verify the interrupting rating and auxiliary wiring before substituting into a panel designed for the 3RV2011-1EA15-ZW97."},{"question":"What are the key specifications of 3RV2011-1EA15-ZW97?","answer":"Trip Class 10, 100 kA breaking at 400 V, 4 kA at 690 V, rated voltage 20–690 V, 45 mm wide, 97 mm deep, screw and snap-on DIN rail mounting, phase failure detection, no ground fault detection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1EA15-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1EA15-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}