{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1EA40","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1EA40","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1EA40","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1EA40","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-1EA40 motor protection circuit breaker, Trip Class 10, 100 kA breaking capacity at 400 V, 45 mm width, screw and snap-on mounting for 35 mm DIN rail.","salesMarkdown":"The same 100 kA holds at 240 V and 500 V; at 690 V it drops to 4 kA, so verify the available fault current if feeding from a 690 V transformer. That's a standard requirement for motor protection in most industrial installations and saves adding an external phase monitor relay. The 45 mm width (one standard module) fits a typical motor starter row alongside a contactor of the same width. Main circuit connection uses ring cable lugs with M3 screws. The control circuit is not separately terminated — this is a self-powered thermal-magnetic breaker, no auxiliary supply needed. ## Sizing and coordination For motor sizing, the 3RV2011-1EA40 covers a specific hp window: 0.33 hp at 230 V, 0.75 hp at 220/230 V, 2 hp at 460/480 V, and 3 hp at 575/600 V. The thermal setting range is not listed explicitly in this record, but the hp ratings define the motor full-load current window it protects. Backup fuse requirements: gL/gG 32 A at 400 V and 500 V, dropping to 25 A at 690 V — the fuses protect the breaker's short-circuit capacity in high-energy faults. Maximum switching frequency is 15 operations per hour in AC-3 duty (motor starting), and the same 15 1/h for AC-3e (enhanced motor starting). That's adequate for most pump, fan, and conveyor cycles; high-repetition applications like rapid indexing may need a contactor rated for more starts per hour.","metaTitle":"Siemens 3RV2011-1EA40 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2011-1EA40 SIRIUS motor protection circuit breaker. Trip Class 10, 100 kA breaking capacity at 400 V, phase failure detection, 45 mm wide. Active production, sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Trip Class":"CLASS 10","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/47365d08c1cde0b18d5908f94ce3e19b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=412221&mlfb=3RV2011-1EA40","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1EA40/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1EA40","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1EA40 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}