{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1FA10-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1FA10-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1FA10-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1FA10-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, size S00, 3RV2011-1FA10-0BA0, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw-type terminals, DIN rail mount.","salesMarkdown":"## Motor protection circuit breaker for the panel builder The breaker integrates phase failure detection, so loss of one phase on a three-phase motor triggers a trip before single-phasing damages the winding. Rated breaking capacity hits 100 kA at 400 V AC and 500 V AC, dropping to 4 kA at 690 V AC. The gG backup fuse coordination at 400 V and 500 V is 32 A; at 690 V it steps down to 25 A. For a motor branch circuit, that tells the panel builder what maximum upstream fuse preserves the breaker's short-circuit ratings. ## DIN-rail footprint and terminal details Main circuit terminals accept 2× (0.75 to 2.5 mm²) solid or stranded, or 2× 4 mm². Screw-type terminals with M3 thread; Pozidriv size 2 screwdriver tip, shaft diameter 5 to 6 mm. Strip length and torque follow standard Siemens SIRIUS practice — no special tooling needed. ## Operating conditions and lifecycle Maximum switching frequency at AC-3 duty is 15 operations per hour. That is a thermal limit of the bimetal trip mechanism, not a contactor wear limit — fine for pump or fan starting cycles, but not for jogging or high-duty conveyor indexing.","metaTitle":"Siemens 3RV2011-1FA10-0BA0 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2011-1FA10-0BA0 SIRIUS motor protection circuit breaker, size S00. Trip Class 10, 100 kA breaking capacity at 400 V, phase failure detection. Active production, sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 400 V":"gG 32 A","at 500 V":"gG 32 A","at 690 V":"gG 25 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-50 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"1.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 500 V rated value":"100 kA","at 690 V rated value":"4 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"500","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"5 A","Of Auxiliary Contacts Typical":"500","Substance Prohibitance (Date)":"10/01/2009","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"5 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"500","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"65 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"3.5 ... 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d87c2827628cc6420c717835f9d23ea2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=386350&mlfb=3RV2011-1FA10-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1FA10-0BA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV2011-1FA10-0BA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"What is the breaking capacity of 3RV2011-1FA10-0BA0?","answer":"100 kA at 240 V, 400 V, and 500 V AC; 4 kA at 690 V AC (6 kA AC at 690 V per the AC rating)."},{"question":"Will 3RV2011-1FA10-0BA0 drop into a panel specified for 3RV2011-0AA10?","answer":"Both are size S00, same 45 mm width and DIN-rail mount, so the physical footprint is identical. The 1FA10 variant carries a higher breaking capacity (100 kA vs the 0AA10's lower rating) and includes phase failure detection — check the trip current setting range matches your motor FLA before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1FA10-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1FA10-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}