{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1GA10-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1GA10-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1GA10-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1GA10-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2011-1GA10-0BA0, Size S00, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw-type terminals, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"## Breaking capacity and back-up fuses Rated breaking capacity hits 100 kA at 400 V AC and 500 V AC, dropping to 6 kA at 690 V AC. For higher-voltage 690 V circuits, the 6 kA rating still covers typical downstream faults. When a higher interrupting rating is needed upstream, the spec calls for back-up fuses: gG 50 A at 400 V, gG 40 A at 500 V, gG 35 A at 690 V. ## Motor power and phase-loss protection Rated motor power at 230 V is 1.5 kW, which gives a quick sizing reference for smaller three-phase motors. The breaker includes phase failure detection — if one phase drops out, it trips before the motor overheats from single-phasing. That's a standard feature on SIRIUS motor-protection breakers and saves adding a separate phase-loss relay. For thermal management in a closed panel, maintain at least 50 mm clearance above and below, 30 mm to the sides, and zero forwards or backwards — that keeps the breaker's self-heating from derating adjacent devices. ## Terminals and wiring Main current circuit uses screw-type terminals, M3 size. Accepts 2× (0.75 to 2.5 mm²) solid or stranded, or 2× 4 mm². Use a Pozidriv size 2 screwdriver with a 5 to 6 mm diameter shaft. The terminal layout is standard for the S00 frame — no surprises for a panel builder familiar with the SIRIUS range.","metaTitle":"Siemens 3RV2011-1GA10-0BA0 SIRIUS Motor Protection CB, Class","metaDescription":"Siemens 3RV2011-1GA10-0BA0 SIRIUS motor protection circuit breaker, Size S00, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw terminals, DIN rail mount. Current lifecycl","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Trip Class":"CLASS 10","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/48bea66f48d9e5d4e0658d13c0612561.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=72066&mlfb=3RV2011-1GA10-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1GA10-0BA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1GA10-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1GA10-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}