{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1GA20-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1GA20-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1GA20-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1GA20-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2011-1GA20-ZW97, CLASS 10 trip, 100 kA breaking capacity at 400 V, spring-loaded terminals, screw and snap-on 35 mm DIN rail mount.","salesMarkdown":"## What this breaker does in the panel It combines a CLASS 10 thermal-magnetic trip curve with phase failure detection, so it protects a three-phase motor from overload, short-circuit, and single-phasing — the most common cause of motor burnouts on a line. The spring-loaded terminals (accepting 2x 0.5 to 4 mm² solid or stranded) speed up panel wiring, and the breaker mounts on a 35 mm DIN rail per DIN EN 60715 with a screw-and-snap-on fastening method, meaning it drops into any standard industrial enclosure without extra brackets. The interrupting rating is 100 kA at 400 V and 500 V, and 4 kA at 690 V. At 240 V it also holds 100 kA. The gL/gG fuse backup ratings are 50 A at 400 V, 40 A at 500 V, and 35 A at 690 V, so if you need to coordinate with a downstream fuse, those are the maximum sizes the breaker will let through without damage. Required clearances: 50 mm upwards, 50 mm downwards, 30 mm at the side, and 0 mm forwards and backwards. That zero forwards clearance means the breaker can be mounted flush against a panel door or gland plate, which is useful when you are packing multiple motor starters into a single enclosure.","metaTitle":"Siemens 3RV2011-1GA20-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV2011-1GA20-ZW97 motor protection circuit breaker, CLASS 10 trip, 100 kA at 400 V, spring terminals, DIN rail mount. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Upwards":"50 mm","Forwards":"0 mm","at 400 V":"gL/gG 50 A","at 500 V":"gL/gG 40 A","at 690 V":"gL/gG 35 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","Mounting Position":"any","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"6.3 A","at 500 V rated value":"100 kA","at 600 V rated value":"6.3 A","at 690 V rated value":"4 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"0.25 hp","at 200/208 V rated value":"1 hp","at 220/230 V rated value":"1.5 hp","at 460/480 V rated value":"3 hp","at 575/600 V rated value":"5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"6.3 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"6.3 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"6.3 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (20 ... 12)","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"82 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"4.5 ... 6.3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=383786&mlfb=3RV2011-1GA20-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1GA20-ZW97/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3RV2011-1GA20-ZW97?","answer":"The 3RV2011-0BA20 is a sibling in the same SIRIUS family, but it lacks the -ZW97 suffix which typically denotes a special variant (e.g., special settings, accessories, or a specific factory configuration). The 3RV2011-1GA20-ZW97 will physically drop into a panel specified for the 3RV2011-0BA20 — same 45 mm width, same DIN rail mount, same spring terminals — but the trip settings or auxiliary contact configuration may differ. Verify the -ZW97 variant's exact release curve and auxiliary wiring before substituting."},{"question":"What are the key ratings of 3RV2011-1GA20-ZW97?","answer":"CLASS 10 trip, 100 kA breaking capacity at 400 V, phase failure detection, spring-loaded terminals, and a rated voltage range of 20 to 690 V. It is rated for motor protection and mounts on a 35 mm DIN rail."},{"question":"Where can I buy 3RV2011-1GA20-ZW97?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1GA20-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1GA20-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}