{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1GA25-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1GA25-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1GA25-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1GA25-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-1GA25-ZW96 motor protection circuit breaker, 6.3 A rated current at 480/600 V, 100 kA breaking capacity at 400 V, Trip Class 10, spring-loaded terminals, 45 mm wide.","salesMarkdown":"## Motor protection circuit breaker, SIRIUS, 6.3 A, 100 kA It carries a rated current of 6.3 A at both 480 V and 600 V, with a massive 100 kA breaking capacity at 400 V — meaning it can safely interrupt fault currents up to that level without cascading damage upstream in the panel. At 45 mm wide, it fits standard 45 mm slot spacing in most motor control centers. Depth is 97 mm, height 106 mm. Clearance requirements: 50 mm upward, 50 mm downward, 30 mm at the side, and 0 mm forward/backward — meaning you can pack it tight front-to-back, but leave breathing room above and below. Spring-loaded terminals on the main circuit accept 2× (0.5 to 2.5 mm²) solid or stranded conductors. No screw torque to verify — just strip, insert, and latch. ## Short-circuit and auxiliary contact ratings Short-circuit breaking capacity varies with voltage: 100 kA at 240 V, 400 V, and 500 V; 4 kA at 690 V. At 400 V and 500 V, the rating assumes upstream gL/gG fuses sized at 50 A and 40 A respectively; at 690 V, a 35 A gL/gG fuse is required. Auxiliary contact (integrated into the ZW96 variant) switches: 1 A at 24 V, 0.15 A at 60 V, 0.5 A at 120/125/230 V. These are the dry-contact ratings for the signal circuit — the 0.5 A at 120 V is typical for PLC input modules. The product lifecycle stage is current — meaning this is an active, in-production catalog item, not a phase-out or NRND part. No last-time-buy concerns; it's a standard BOM line.","metaTitle":"Siemens 3RV2011-1GA25-ZW96 SIRIUS Circuit Breaker, 6.3 A, 10","metaDescription":"Siemens SIRIUS 3RV2011-1GA25-ZW96 motor protection circuit breaker. 6.3 A rated current, 100 kA breaking capacity at 400 V. Trip Class 10. Spring-loaded terminals. Active productio","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 400 V":"gL/gG 50 A","at 500 V":"gL/gG 40 A","at 690 V":"gL/gG 35 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"6.3 A","at 500 V rated value":"100 kA","at 600 V rated value":"6.3 A","at 690 V rated value":"4 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"spring-loaded terminals","at 110/120 V rated value":"0.25 hp","at 200/208 V rated value":"1 hp","at 220/230 V rated value":"1.5 hp","at 460/480 V rated value":"3 hp","at 575/600 V rated value":"5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"6.3 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"6.3 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"6.3 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (20 ... 12)","For Auxiliary And Control Circuit":"spring-loaded terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","for AWG cables for auxiliary contacts":"2x (20 ... 14)","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","Finely Stranded Without Core End Processing":"2x (0.5 ... 1.5 mm²)","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"82 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"4.5 ... 6.3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/709cac837a148652c7873ba69809a49c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=622688&mlfb=3RV2011-1GA25-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1GA25-ZW96/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV2011-1GA25-ZW96 at 400 V?","answer":"100 kA at 400 V, with an upstream 50 A gL/gG fuse."},{"question":"What is the rated current of 3RV2011-1GA25-ZW96?","answer":"6.3 A at both 480 V and 600 V."},{"question":"Does 3RV2011-1GA25-ZW96 include phase failure detection?","answer":"Yes, phase failure detection is built in."},{"question":"What is the mounting width of 3RV2011-1GA25-ZW96?","answer":"45 mm, fitting a standard 45 mm DIN-rail slot."},{"question":"Where can I buy 3RV2011-1GA25-ZW96?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1GA25-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1GA25-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}