{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1HA10-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1HA10-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1HA10-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1HA10-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2011-1HA10-ZW96, 45 mm wide, 100 kA breaking capacity at 400 V, Trip Class 10, screw-type terminals.","salesMarkdown":"## Motor protection circuit breaker, 45 mm width, 100 kA SCCR The part detects phase failure as standard, with no ground-fault detection built in. Rated voltage covers 20 to 690 V AC. Motor horsepower ratings: 0.33 hp at 110/120 V, 1 hp at 230 V, 2 hp at 200/208 V and 220/230 V, 5 hp at 460/480 V. At 480 V the continuous current rating is 8 A; at 600 V it is also 8 A. The maximum switching frequency at AC-3 duty is 15 operations per hour. The backup fuse ratings for this breaker: gL/gG 50 A at 400 V, gL/gG 40 A at 500 V, and gL/gG 35 A at 690 V. Minimum clearance requirements: 50 mm upwards, 50 mm downwards, 30 mm at the sides, and zero forwards or backwards — so it can sit flush against a panel backplate or enclosure door. Terminals are screw-type for the main current circuit, accepting 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm². Main contact screws are M3. The overall dimensions are 97 mm high, 45 mm wide, and 97 mm deep.","metaTitle":"Siemens 3RV2011-1HA10-ZW96 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV2011-1HA10-ZW96 motor protection circuit breaker, 100 kA SCCR at 400 V, Trip Class 10, 45 mm wide. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 400 V":"gL/gG 50 A","at 500 V":"gL/gG 40 A","at 690 V":"gL/gG 35 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"1 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"8 A","at 500 V rated value":"42 kA","at 600 V rated value":"8 A","at 690 V rated value":"4 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","at 110/120 V rated value":"0.33 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"2 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"42 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"8 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"8 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"3.1 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"104 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"5.5 ... 8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8d6b17ca3a4db2579f4f8036847dcf8f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=315752&mlfb=3RV2011-1HA10-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1HA10-ZW96/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the 3RV2011-1HA10-ZW96?","answer":"It is a Trip Class 10 motor protection circuit breaker with 100 kA breaking capacity at 400 V, 45 mm width, rated voltage 20 to 690 V, and phase failure detection. Horsepower ratings cover 0.33 hp at 120 V up to 5 hp at 480 V."},{"question":"Will the 3RV2011-1HA10-ZW96 drop into a panel specified around the 3RV2011-0AA10?","answer":"Both are 45 mm wide SIRIUS motor protection breakers with the same DIN-rail mounting and screw-type terminals, so the physical swap is straightforward. Verify the current and trip-class settings match the motor nameplate — the -ZW96 suffix may indicate a special setting range."},{"question":"Where can I buy the 3RV2011-1HA10-ZW96 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1HA10-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1HA10-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}