{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1JA15-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1JA15-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1JA15-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1JA15-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, 3RV2011-1JA15-ZW97, Class 10 trip, 100 kA breaking capacity at 400 V, phase failure detection, 45 mm wide, DIN rail mount.","salesMarkdown":"## What it is and what it does The Siemens 3RV2011-1JA15-ZW97 is a SIRIUS motor protection circuit breaker designed to protect motors and feeders against overload and short-circuit. It is a current-production part, still in active manufacture. Rated for Class 10 trip characteristics, it clears overloads fast enough to protect standard induction motors during stall or jam conditions. Phase failure detection is built in, so a lost phase on the line side trips the breaker before single-phasing damages the motor windings. The interrupting rating at 400 V is 100 kA, which means it can safely clear a bolted fault up to that level without rupturing or cascading to upstream devices. At 690 V the rating drops to 4 kA, still adequate for most industrial distribution systems. ## Mounting and integration Mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715. The 45 mm width (three module spaces) fits standard enclosure rail. Any mounting position is allowed, so it can be installed sideways in tight gland-plate areas without derating. Depth is 97 mm, height 97 mm — a compact cube that leaves room alongside contactors and relays in a motor control center bucket.","metaTitle":"Siemens 3RV2011-1JA15-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2011-1JA15-ZW97 SIRIUS motor protection circuit breaker, Class 10 trip, 100 kA breaking at 400 V. Phase failure detection, DIN rail mount. Current production. Sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 400 V":"gL/gG 50 A","at 500 V":"gL/gG 40 A","at 690 V":"gL/gG 40 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"1.5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"10 A","at 500 V rated value":"42 kA","at 600 V rated value":"10 A","at 690 V rated value":"4 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"10 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"42 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"10 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"10 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"10 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"3.1 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"130 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9a3a657c3db3ea8f4595361d8ac3d05b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=369973&mlfb=3RV2011-1JA15-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1JA15-ZW97/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV2011-1JA15-ZW97 and how do I get a price?","answer":"Sourced to order against an RFQ through independent distribution. Submit a quote request; availability and current pricing are confirmed at quote time."},{"question":"What is 3RV2011-1JA15-ZW97's listed depth?","answer":"Depth is 97 mm. Width is 45 mm, height is 97 mm."},{"question":"What compliance documentation does this part carry?","answer":"The evidence does not list specific compliance certificates (RoHS, REACH, UL, IEC). Standard Siemens SIRIUS breakers typically carry IEC/EN 60947-2 and UL 489 certifications, but confirm for this specific variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1JA15-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1JA15-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}