{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-1KA10-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-1KA10-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-1KA10-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1KA10-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2011-1KA10-0BA0 motor protection circuit breaker, frame size S00, CLASS 10 trip, 100 kA breaking capacity at 400 V AC, screw and snap-on DIN rail mounting.","salesMarkdown":"The breaker has phase failure detection built in, which ensures that loss of one phase causes a trip rather than single-phasing the motor. Rated voltage covers 20 to 690 V, so it works across low-voltage motor circuits from 24 V control transformers up to 690 V industrial mains. The gG fuse backup ratings (63 A at 400 V, 50 A at 500 V, 40 A at 690 V) tell you the maximum upstream fuse that still allows the breaker to clear a fault within its rated capacity — important for selectivity coordination. Clearance requirements: 50 mm above and below, 30 mm to the side, and zero forwards or backwards clearance needed, meaning it can sit flush against the back panel or a busbar. Screw-type terminals accept 2 × (0.75 to 2.5 mm²) solid/stranded or 2 × 4 mm², with M3 screws and a 5–6 mm screwdriver shaft. Mounting position is any, so horizontal or vertical rail orientation works.","metaTitle":"Siemens SIRIUS 3RV2011-1KA10-0BA0 Motor Protection Circuit B","metaDescription":"Siemens 3RV2011-1KA10-0BA0 SIRIUS motor protection circuit breaker, frame size S00, CLASS 10 trip, 100 kA breaking at 400 V. Screw/snap-on DIN rail. Available to order, quoted on r","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Trip Class":"CLASS 10","Product Status":"Active","Temp Operating Max":"60 °C","Temp Operating Min":"-20 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bb369301028b932a3a3a2f9ff3ac869d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=29127&mlfb=3RV2011-1KA10-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-1KA10-0BA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-1KA10-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-1KA10-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}