{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-4AA10-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-4AA10-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-4AA10-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-4AA10-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2011-4AA10-ZW97, Class 10 trip, 100 kA breaking capacity at 240 V, 45 mm width, screw and snap-on DIN rail mount.","salesMarkdown":"No ground fault detection here — that's a separate add-on if your line needs it. The interrupting ratings tell you where this breaker can sit in the fault hierarchy: 100 kA at 240 V, 30 kA at 400 V, 5 kA at 500 V, 2 kA at 690 V. At 240 V it's a monster — you can put it upstream of a sub-panel and not worry about series rating gymnastics. At 690 V the 2 kA limit means it's fine for most motor branch circuits but check your available fault current if you're feeding from a large transformer. The fuse backup table (gL/gG 80 A at 240 V, 63 A at 400 V, 50 A at 500 V, 40 A at 690 V) gives the maximum upstream fuse that still allows the breaker to clear its rated fault — useful for selectivity coordination studies. Horsepower ratings: 1 hp at 110/120 V, 2 hp at 230 V, 3 hp at 200/208 V, 5 hp at 220/230 V. That covers the common small-motor sizes you'd find on pumps, fans, and small conveyors in a 480 V or 240 V delta panel. The AC-3 maximum switching rate is 15 operations per hour — fine for a start/run/stop cycle, not for jogging or frequent reversing. Width is 45 mm, depth 97 mm, height 97 mm — that's a standard 2-module-wide footprint on a 35 mm DIN rail per DIN EN 60715. Screw and snap-on mounting: clip it onto the rail, tighten the screw to lock it, no tools for the rail engagement. Mounting position is any, so you can lay it sideways in a shallow enclosure if the gland plate forces that. Terminals are screw-type for the main current circuit, accepting 2x 0.75...2.5 mm² solid or stranded, or 2x 4 mm². Main contact screws are M3. That's enough for the motor branch circuit wiring typical of a 5 hp motor at 230 V. Temperature compensation is active across the full operating range of -20 to +60 °C — the thermal trip curve stays accurate whether the panel is in a conditioned room or a hot pump house.","metaTitle":"Siemens 3RV2011-4AA10-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV2011-4AA10-ZW97 motor protection circuit breaker. Class 10, 100 kA at 240 V, 30 kA at 400 V. DIN rail mount. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 240 V":"gL/gG 80 A","at 400 V":"gL/gG 63 A","at 500 V":"gL/gG 50 A","at 690 V":"gL/gG 40 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"2 hp","at 240 V rated value":"100 kA","at 400 V rated value":"30 kA","at 480 V rated value":"16 A","at 500 V rated value":"5 kA","at 600 V rated value":"16 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","at 110/120 V rated value":"1 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"5 hp","at 460/480 V rated value":"10 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"55 kA","at AC at 500 V rated value":"10 kA","at AC at 690 V rated value":"4 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"16 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"16 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"3.1 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"208 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"10 ... 16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/673a1413f046deac6adf7ea5c2b532ef.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=552693&mlfb=3RV2011-4AA10-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-4AA10-ZW97/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV2011-4AA10-ZW97 at 400 V?","answer":"30 kA at 400 V. At 240 V it's 100 kA, at 500 V it's 5 kA, at 690 V it's 2 kA."},{"question":"What is the trip class of this motor protection breaker?","answer":"Class 10 — trips within 10 seconds at 7.2× the thermal setting, standard for protecting general-purpose induction motors."},{"question":"Where can I buy 3RV2011-4AA10-ZW97?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-4AA10-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-4AA10-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}