{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2011-4AA10-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2011-4AA10-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV2011-4AA10-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2011-4AA10-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, 3RV2011-4AA10-ZX95, Class 10, 45 mm width, 97 mm depth, screw and snap-on mounting onto 35 mm DIN rail, 30 kA at 400 V.","salesMarkdown":"The gL/gG fuse coordination at 400 V is 63 A, so the upstream fuse clears before the breaker takes thermal damage on a hard short. ## Integration notes Screw-type terminals on the main current circuit accept 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm². Main contact screws are M3. Clearances: 50 mm upwards and downwards, 30 mm at the sides, 0 mm forwards and backwards.","metaTitle":"Siemens 3RV2011-4AA10-ZX95 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV2011-4AA10-ZX95 motor protection circuit breaker, Class 10 trip, 45 mm width, 97 mm depth. Screw/snap-on 35 mm DIN rail. Rated 30 kA at 400 V. Phase failure detec","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 240 V":"gL/gG 80 A","at 400 V":"gL/gG 63 A","at 500 V":"gL/gG 50 A","at 690 V":"gL/gG 40 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"2 hp","at 240 V rated value":"100 kA","at 400 V rated value":"30 kA","at 480 V rated value":"16 A","at 500 V rated value":"5 kA","at 600 V rated value":"16 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"1 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"5 hp","at 460/480 V rated value":"10 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"55 kA","at AC at 500 V rated value":"10 kA","at AC at 690 V rated value":"4 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"16 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"16 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"16 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 ... 14), 2x 12","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"3.1 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"208 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"10 ... 16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ba3cb6370a59bfb72a906f6f6bf9719.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=553523&mlfb=3RV2011-4AA10-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2011-4AA10-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV2011-4AA10-ZX95 and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 3RV2011-4AA10-ZX95's listed depth (97 mm) on this component line?","answer":"The depth is 97 mm, width 45 mm, height 97 mm. Mounts on 35 mm DIN rail with 50 mm clearance above and below, 30 mm at the sides."},{"question":"What is 3RV2011-4AA10-ZX95's listed width (45 mm) on this component line?","answer":"Width is 45 mm, depth 97 mm, height 97 mm. Fits a standard 45 mm wide DIN-rail slot."},{"question":"Will 3RV2011-4AA10-ZX95 drop into a panel that was specified around 3RV1011-1HA10 without rewiring?","answer":"Both are 45 mm wide SIRIUS motor protection breakers with screw-type terminals on 35 mm DIN rail, so the footprint and mounting are compatible. However, verify the trip curve and clearing capacity match the application—this unit is Class 10 with 30 kA at 400 V."},{"question":"What compliance documentation does this brand provide for 3RV2011-4AA10-ZX95 (RoHS, REACH, UL, IEC)?","answer":"The product is a Siemens SIRIUS circuit breaker designed to IEC/EN 60947 standards. Compliance documentation (RoHS, REACH, UL) is available from Siemens upon request; the part carries CE marking for the European market."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2011-4AA10-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2011-4AA10-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}