{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2021-1AA10-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2021-1AA10-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RV2021-1AA10-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2021-1AA10-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2021-1AA10-ZW96 motor protection circuit breaker, Trip Class 10, 100 kA breaking capacity at 400 V AC, 45 mm wide, screw and snap-on DIN rail mounting.","salesMarkdown":"The 100 kA breaking capacity at 240 V, 400 V, 500 V, and 690 V AC means this breaker handles high prospective fault currents common in industrial distribution — it's rated for installation at the motor branch, not just downstream of a current-limiting fuse. The Trip Class 10 means the thermal trip element will open within 10 seconds at 7.2× the thermal setting current, matching standard IEC 60947-4-1 requirements for motor starting duty. No ground fault detection, so that function must come from a separate device or upstream GFCI. The screw and snap-on mechanism onto 35 mm DIN rail means it clips on without tools and can be screw-fastened for vibration resistance. Clearance requirements: 50 mm upward and downward, 30 mm to the side, 0 mm forward and backward (–,) — so it can be stacked tight front-to-back but needs breathing space above and below for thermal dissipation. Terminal capacity on the main contacts accepts 2× (1 to 2.5 mm²) or 2× (2.5 to 10 mm²) solid or stranded, with M4 screw terminals.","metaTitle":"Siemens 3RV2021-1AA10-ZW96 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2021-1AA10-ZW96 SIRIUS motor protection circuit breaker. Trip Class 10, 100 kA breaking capacity at 400 V, phase failure detection. Current production. Quoted on request","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2021-1AA10-ZW96","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S0 for motor protection, Class 10 A-release 1.1...1.6 A N-release 21 A Screw terminal Standard switching capacity Multi-unit packaging Pack = 24 units","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M4","Mounting Position":"any","Solid Or Stranded":"2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"1.6 A","at 500 V rated value":"100 kA","at 600 V rated value":"1.6 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 460/480 V rated value":"1 hp","at 575/600 V rated value":"0.8 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S0","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"1.6 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"1.6 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1.6 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (16 ... 12), 2x (14 ... 8)","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"2 ... 2.5 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"21 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.1 ... 1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/69e3aae776a3a972c11948ccacc118a3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=277152&mlfb=3RV2021-1AA10-ZW96"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV2021-1AA10-ZW96?","answer":"The 3RV2021-1AA10-ZW96 has a 100 kA breaking capacity at 240 V, 400 V, 500 V, and 690 V AC, covering the full range of common industrial supply voltages."},{"question":"Will 3RV2021-1AA10-ZW96 drop into a panel designed for 3RV2011-0AA10?","answer":"The 3RV2021-1AA10-ZW96 shares the same 45 mm width and DIN rail mounting as the 3RV2011-0AA10, so it will physically fit the same rail position. However, verify the terminal arrangement and the thermal setting range — the 3RV2021 series has different overload characteristics and breaking capacity. No rewiring is guaranteed only if the existing wire sizes and terminal types match the M4 screw terminals accepting 2× (1 to 2.5 mm²) or 2× (2.5 to 10 mm²)."},{"question":"What compliance documentation is available for 3RV2021-1AA10-ZW96?","answer":"As a Siemens SIRIUS product, the 3RV2021-1AA10-ZW96 is designed to meet IEC 60947-4-1 for motor protection circuit breakers. Standard documentation includes a CE declaration of conformity and RoHS/REACH compliance statements. UL/CSA listings are typical for this series but should be confirmed against the specific variant suffix (ZW96) at order time."},{"question":"Where can I buy 3RV2021-1AA10-ZW96 and how is it quoted?","answer":"The 3RV2021-1AA10-ZW96 is sourced through independent industrial distribution channels. It is quoted to order against an RFQ — submit your target quantity and delivery window, and availability with current pricing will be confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2021-1AA10-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2021-1AA10-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}