{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2021-1DA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2021-1DA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2021-1DA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2021-1DA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2021-1DA10, motor protection circuit breaker, Class 10, 100 kA breaking capacity at 400 V AC, screw-type terminals, 45 mm wide.","salesMarkdown":"It is part of the SIRIUS family, a modular system for motor feeders and control circuits. Rated for Class 10 trip characteristics, it clears overloads quickly enough to protect standard motors during start-up, while the integrated phase failure detection ensures the motor drops out if one supply phase is lost — a common cause of single-phasing damage. Breaking capacity is 100 kA at 400 V AC and 500 V AC, dropping to 10 kA at 690 V AC. The 45 mm width (3 module spaces) fits standard enclosure rail layouts, and the 97 mm depth leaves clearance for wiring behind the panel door. Screw-type terminals on the main circuit accept 2x (1 to 2.5 mm²) solid/stranded or 2x (2.5 to 10 mm²) — sized for motor feeder cables up to 10 mm². Mounting position is any orientation, so it works in tight side-entry panels. No official successor has been announced, so the 3RV2021-1DA10 remains the direct fit for any existing SIRIUS motor feeder design. If you are stocking a spare for a legacy panel, this is the one to put in the cabinet.","metaTitle":"Siemens 3RV2021-1DA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2021-1DA10 SIRIUS motor protection circuit breaker, Class 10 trip, 100 kA breaking capacity at 400 V AC, phase failure detection, screw & snap-on DIN rail mount. Current","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2021-1DA10","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S0 for motor protection, CLASS 10 A-release 2.2...3.2 A N release 42 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M4","Mounting Position":"any","Solid Or Stranded":"2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.25 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"3.2 A","at 500 V rated value":"100 kA","at 600 V rated value":"3.2 A","at 690 V rated value":"10 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.1 hp","at 200/208 V rated value":"0.5 hp","at 220/230 V rated value":"0.75 hp","at 460/480 V rated value":"2 hp","at 575/600 V rated value":"2 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"10 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S0","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"3.2 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"3.2 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"3.2 A","at AWG cables for main contacts":"2x (16 ... 12), 2x (14 ... 8)","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"2 ... 2.5 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"42 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.2 ... 3.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$34.29 – $83.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/69e3aae776a3a972c11948ccacc118a3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=455445&mlfb=3RV2021-1DA10"},"ai":{"faq":[{"question":"What are the key ratings for motor protection?","answer":"Class 10 trip curve, phase failure detection, and a breaking capacity of 100 kA at 400 V AC. Motor horsepower ratings range from 0.1 hp at 110/120 V up to 2 hp at 460/480 V and 575/600 V."},{"question":"What is the physical size and mounting?","answer":"Width 45 mm, height 97 mm, depth 97 mm. Mounts on 35 mm DIN rail per DIN EN 60715 via screw or snap-on. Any mounting position is allowed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2021-1DA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2021-1DA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}