{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2021-1HA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2021-1HA15","canonicalUrl":"https://aoctrl.com/siemens/3RV2021-1HA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2021-1HA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2021-1HA15 motor protection circuit breaker, CLASS 10, 100 kA breaking capacity at 400 V, screw terminals, 45 mm wide, for 35 mm DIN rail.","salesMarkdown":"The 3RV2021-1HA15: Trip class CLASS 10 means it disconnects within 10 seconds at 7.2× the thermal setting current, fast enough to protect standard IEC motor windings during a locked-rotor event. Breaking capacity is 100 kA at 400 V and 240 V, 42 kA at 500 V, and 4 kA at 690 V. At 480 V it is rated 8 A; at 600 V also 8 A. These figures cover most industrial distribution levels up to the 690 V class, meaning the breaker can interrupt bolted faults on a 400 V bus without upstream fusing — useful for a line-side disconnect in a motor control center. Width is 45 mm — occupies one standard 45 mm modular slot. Any mounting position is permitted. Screw-type terminals for the main circuit accept 2x (0.5…1.5 mm²) or 2x (0.75…2.5 mm²) solid or stranded wire. The part is qualified for the full industrial temperature envelope. Depth is 97 mm, height 97 mm, width 45 mm. Clearance requirements: 50 mm upwards, 50 mm downwards, 30 mm at the side, 0 mm forwards and backwards. This means the breaker can be mounted flush against a backpanel or enclosure wall on the forward/backward axis, but needs 50 mm above and below for air circulation and arc-quenching clearance. Maximum switching frequency at AC-3 and AC-3e duty is 15 operations per hour. That is typical for a motor-starting application — adequate for a conveyor, pump, or fan cycling a few times per hour, but not for a rapid-cycling press or servo spindle.","metaTitle":"Siemens 3RV2021-1HA15 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2021-1HA15 SIRIUS motor protection circuit breaker. CLASS 10 trip, 100 kA breaking at 400 V. Screw terminals, DIN rail mount. Current production. Sourced to order agains","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M4","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"1 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"8 A","at 500 V rated value":"42 kA","at 600 V rated value":"8 A","at 690 V rated value":"4 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.33 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"2 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"42 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S0","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"8 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"8 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"8 A","at AWG cables for main contacts":"2x (16 ... 12), 2x (14 ... 8)","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"3.1 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"2 ... 2.5 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"104 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"5.5 ... 8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$41.91","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/69e3aae776a3a972c11948ccacc118a3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=319855&mlfb=3RV2021-1HA15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2021-1HA15/alternatives.json"},"ai":{"faq":[{"question":"What is the width and depth of 3RV2021-1HA15?","answer":"Width is 45 mm, depth is 97 mm, height is 97 mm. It occupies one standard 45 mm DIN-rail slot."},{"question":"Can 3RV2021-1HA15 be mounted on a DIN rail?","answer":"Yes, it mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715. Any mounting position is permitted."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2021-1HA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2021-1HA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}