{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2021-4AA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2021-4AA15","canonicalUrl":"https://aoctrl.com/siemens/3RV2021-4AA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2021-4AA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2021-4AA15 motor protection circuit breaker, CLASS 10, 100 kA at 240 V, 45 mm wide, screw and snap-on DIN rail mount.","salesMarkdown":"It provides phase failure detection and is rated for operating voltages from 20 to 690 V. The 3RV2021-4AA15 delivers a breaking capacity of 100 kA at 240 V rated value — that is the short-circuit current it can safely interrupt at that voltage. At 400 V rated value the breaking capacity is 25 kA, and at 690 V rated value it drops to 2 kA. For motor sizing, it is rated at 2 hp at 230 V rated value, and carries a rated current of 16 A at both 480 V and 600 V rated values. The trip class is CLASS 10, meaning it will trip within 10 seconds at 7.2× the thermal setting — standard for protecting standard induction motors during startup. The breaker measures 45 mm wide, 97 mm deep, and 97 mm high. Required clearances for heat dissipation: 50 mm upwards, 50 mm downwards, and 30 mm at the side. It accepts solid or stranded conductors: 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²). Main contact terminals are M4 screws.","metaTitle":"Siemens SIRIUS 3RV2021-4AA15 Motor Protection Circuit Breake","metaDescription":"Siemens SIRIUS 3RV2021-4AA15 motor protection circuit breaker, CLASS 10 trip, 100 kA breaking capacity at 240 V, 45 mm wide, screw and snap-on DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2021-4AA15","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 400 V":"gL/gG 63 A","at 500 V":"gL/gG 50 A","at 690 V":"gL/gG 40 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S0 for motor protection, CLASS 10 A-release 10...16 A N-release 208 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M4","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"2 hp","at 240 V rated value":"100 kA","at 400 V rated value":"25 kA","at 480 V rated value":"16 A","at 500 V rated value":"5 kA","at 600 V rated value":"16 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"1 hp","at 200/208 V rated value":"3 hp","at 220/230 V rated value":"5 hp","at 460/480 V rated value":"10 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"55 kA","at AC at 500 V rated value":"10 kA","at AC at 690 V rated value":"4 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S0","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"16 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"16 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"16 A","at AWG cables for main contacts":"2x (16 ... 12), 2x (14 ... 8)","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"3.1 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"2 ... 2.5 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"208 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"10 ... 16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$48.26 – $110.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/69e3aae776a3a972c11948ccacc118a3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=497510&mlfb=3RV2021-4AA15"},"ai":{"faq":[{"question":"What is the breaking capacity at 240 V?","answer":"The breaking capacity is 100 kA at 240 V rated value."},{"question":"What is the trip class?","answer":"The trip class is CLASS 10, meaning it trips within 10 seconds at 7.2× the thermal setting."},{"question":"Does it detect phase failure?","answer":"Yes, phase failure detection is included."},{"question":"What are the mounting dimensions?","answer":"Width 45 mm, depth 97 mm, height 97 mm. Requires 50 mm clearance upwards and downwards, and 30 mm at the side."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2021-4AA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2021-4AA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}