{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2021-4AA15-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2021-4AA15-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RV2021-4AA15-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2021-4AA15-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2021-4AA15-ZW97, Class 10, 16 A rated current at 480/600 V, 25 kA breaking capacity at 400 V, screw and snap-on DIN rail mount.","salesMarkdown":"The Siemens SIRIUS 3RV2021-4AA15-ZW97 is a motor protection circuit breaker designed for Class 10 trip characteristics, meaning it disconnects within 10 seconds at 7.2x the thermal setting — fast enough to protect standard induction motors during locked-rotor events without nuisance tripping on normal starts. It carries a 16 A rated current at both 480 V and 600 V, and delivers a 25 kA breaking capacity at 400 V, so it can safely interrupt high-fault currents in a motor branch circuit without upstream fuses needing to clear first. ## Breaking capacity and fuse coordination The 3RV2021-4AA15-ZW97 is rated for use with upstream gL/gG fuses up to 63 A at 400 V, 50 A at 500 V, and 40 A at 690 V. At 240 V the breaker handles 100 kA, so it's comfortable on 208/240 V systems with high transformer fault current. The integrated auxiliary contact is rated 1 A at 24 V, 0.5 A at 120/125/230 V, and 0.15 A at 60 V. These are the switching capacities for the built-in signal contact — useful for feeding a PLC input or a status lamp. The 1 A at 24 V DC is enough for most 24 VDC control circuits, but at 60 V the contact derates sharply to 0.15 A, so don't plan on switching a 60 VDC solenoid directly through it. ## Environmental and wiring The main contact terminals accept M4 screws, and the conductor cross-section accommodates 2x (0.5 to 2.5 mm²) solid or stranded. For compliance documentation, the SIRIUS series carries the usual Siemens declarations (CE, UL, CSA, IEC 60947), though specific cert numbers are not in this listing.","metaTitle":"Siemens 3RV2021-4AA15-ZW97 SIRIUS Motor Protection Circuit B","metaDescription":"Siemens 3RV2021-4AA15-ZW97 SIRIUS motor protection circuit breaker, Class 10 trip, 16 A rated at 480/600 V, 25 kA breaking at 400 V. Phase failure detection, DIN rail mount. Availa","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Trip Class":"CLASS 10","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/69e3aae776a3a972c11948ccacc118a3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=326865&mlfb=3RV2021-4AA15-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2021-4AA15-ZW97/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2021-4AA15-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2021-4AA15-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}