{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2021-4EA15-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2021-4EA15-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RV2021-4EA15-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2021-4EA15-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2021-4EA15-ZX95 motor protection circuit breaker, Trip Class 10, screw and snap-on mounting onto 35 mm DIN rail, width 45 mm, depth 97 mm.","salesMarkdown":"## Motor protection circuit breaker, Trip Class 10, DIN rail mount Mounting position any. Fastening for main contacts uses M4 screws. Conductor cross-section: 2x (0.5... 1.5 mm²) solid or stranded, or 2x (0.75... 2.5 mm²). Minimum clearance distances: 50 mm upwards and downwards, 30 mm at the side, 0 mm forwards and backwards — so it can be packed tight against the back panel and adjacent devices on the rail.","metaTitle":"Siemens SIRIUS 3RV2021-4EA15-ZX95 Motor Protection Circuit B","metaDescription":"Siemens SIRIUS 3RV2021-4EA15-ZX95 motor protection circuit breaker. Trip Class 10, screw/snap-on 35 mm DIN rail. Rated 100 kA at 240 V, 25 kA at 400 V. Width 45 mm. Quoted to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 400 V":"gL/gG 63 A","at 500 V":"gL/gG 63 A","at 690 V":"gL/gG 63 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M4","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"25 kA","at 480 V rated value":"32 A","at 500 V rated value":"5 kA","at 600 V rated value":"32 A","at 690 V rated value":"2 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"2 hp","at 200/208 V rated value":"7.5 hp","at 220/230 V rated value":"10 hp","at 460/480 V rated value":"20 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"55 kA","at AC at 500 V rated value":"10 kA","at AC at 690 V rated value":"4 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S0","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"13.25 W","at AC-3 at 400 V rated value":"32 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"32 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"32 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (16 ... 12), 2x (14 ... 8)","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"4.4 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"2 ... 2.5 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"400 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"27 ... 32 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/69e3aae776a3a972c11948ccacc118a3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=187925&mlfb=3RV2021-4EA15-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2021-4EA15-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3RV2021-4EA15-ZX95 and how is it quoted for volume purchases?","answer":"It is sourced and quoted to order against an RFQ through independent distribution channels; availability and current pricing are confirmed at quote time."},{"question":"What is 3RV2021-4EA15-ZX95's listed depth?","answer":"The listed depth is 97 mm."},{"question":"What is 3RV2021-4EA15-ZX95's listed width?","answer":"The listed width is 45 mm."},{"question":"Will 3RV2021-4EA15-ZX95 drop into a panel specified around 3RV1011-1HA10 without rewiring?","answer":"Both are motor protection circuit breakers from the Siemens SIRIUS family, but the 3RV2021-4EA15-ZX95 has a 45 mm width versus the 3RV1011-1HA10's narrower 45 mm? (Note: 3RV1011-1HA10 width is not in evidence; the 3RV2021-4EA15-ZX95 width is 45 mm. Panel fit should be verified against the existing cutout and wiring — the 3RV2021-4EA15-ZX95 uses M4 main contact screws and accepts 2x (0.5...1.5 mm²) or 2x (0.75...2.5 mm²) conductors, so rewiring may be needed if the original used different terminals.)"}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2021-4EA15-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2021-4EA15-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}