{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2032-4RA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2032-4RA15","canonicalUrl":"https://aoctrl.com/siemens/3RV2032-4RA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2032-4RA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2032-4RA15, CLASS 10, rated 20-690 V, 160 kA breaking capacity at 400 V, screw terminals, 55 mm wide, DIN rail mount.","salesMarkdown":"## Motor protection circuit breaker for panel integration The Siemens 3RV2032-4RA15 is a SIRIUS motor protection circuit breaker designed for Class 10 trip response, meaning it disconnects within 10 seconds at 7.2× the thermal setting — fast enough to protect standard induction motors against locked-rotor events without nuisance tripping on normal starts. It carries a rated operational voltage range of 20 to 690 V and delivers a breaking capacity of 160 kA at 400 V, 125 kA at 500 V, and 100 kA at 690 V, so it can interrupt high-fault currents in industrial distribution without upstream coordination. The auxiliary contact block supports 1 A at 24 V, 0.15 A at 60 V, and 0.5 A at 230 V, covering PLC-level signal feedback. Main circuit terminals are M6 screw-type, accepting 2×(0.5–1.5 mm²) or 2×(0.75–2.5 mm²) solid or stranded conductors.","metaTitle":"Siemens 3RV2032-4RA15 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2032-4RA15 SIRIUS motor protection circuit breaker, CLASS 10 trip, 20-690 V, 160 kA at 400 V, screw terminals, DIN rail. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"149 mm","Width":"55 mm","title":"3RV2032-4RA15","Height":"140 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","at 110 V":"0 A","at 125 V":"0 A","at 220 V":"0 A","at 230 V":"0.5 A","at 240 V":"none required","at 400 V":"160","at 500 V":"125","at 690 V":"100","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"10 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S2 for motor protection, CLASS 10 A-release 70...80 A N-release 1040 A screw terminal increased switching capacity with transverse auxiliary switches 1 NO+1 NC","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"M6","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"15 hp","at 240 V rated value":"100 kA","at 400 V rated value":"50 kA","at 480 V rated value":"77 A","at 500 V rated value":"8 kA","at 600 V rated value":"77 A","at 690 V rated value":"4 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"7.5 hp","at 200/208 V rated value":"25 hp","at 220/230 V rated value":"30 hp","at 460/480 V rated value":"60 hp","at 575/600 V rated value":"75 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"10 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S2","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"20 000","at AC in hot operating state":"29.5 W","at AC-3 at 400 V rated value":"80 A","Of Auxiliary Contacts Typical":"20 000","Substance Prohibitance (Date)":"03/01/2017","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"80 A","at AWG cables for main contacts":"2x (18 ... 2), 1x (18 ... 1)","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"9.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"3 ... 4.5 N·m","with high demand rate according to SN 31920":"50 %","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms Sinus","Electrical Endurance (Switching Cycles) Typical":"20 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S2","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"1 040 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"70 ... 80 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4ac59e9ee2ba9ac36caaae3b52a6bf06.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=125574&mlfb=3RV2032-4RA15"},"ai":{"faq":[{"question":"Where can I buy 3RV2032-4RA15 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability."},{"question":"What is the breaking capacity of 3RV2032-4RA15 at 400 V?","answer":"160 kA at 400 V, with 125 kA at 500 V and 100 kA at 690 V."},{"question":"What trip class is 3RV2032-4RA15?","answer":"CLASS 10 — disconnects within 10 seconds at 7.2× the thermal setting, suitable for standard motor starting profiles."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2032-4RA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2032-4RA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}