{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2041-4YA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2041-4YA15","canonicalUrl":"https://aoctrl.com/siemens/3RV2041-4YA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2041-4YA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV2041-4YA15, CLASS 10 trip, 100 kA at 240 V, screw-type terminals, snap-on DIN rail.","salesMarkdown":"The CLASS 10 trip class means the breaker will trip within 10 seconds at 600% of the thermal setting — this is the standard protection for standard squirrel-cage induction motors; a CLASS 20 would allow longer start times for high-inertia loads, but CLASS 10 is the default for most pump, fan, and compressor applications. The interrupting ratings vary by voltage: 100 kA at 240 V, 30 kA at 400 V, 4 kA at 500 V, and 3 kA at 690 V — ensure the available fault current at the installation point does not exceed the rating at the system voltage. The auxiliary contact ratings are 1 A at 24 V, 0.15 A at 60 V, and 0.5 A at 230 V — sufficient for signaling to a PLC input or contactor coil, but verify the connected load does not exceed these values. ## Panel integration Snap-on mounting onto 35 mm DIN rail per DIN EN 60715, in any mounting position, with a width of 70 mm, height of 165 mm, and depth of 176 mm. Screw-type terminals on the main circuit accept solid or stranded conductors: 2x (2.5 to 16 mm²) or 1x (10 to 70 mm²) — sized for motor branch circuit wiring.","metaTitle":"Siemens 3RV2041-4YA15 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens SIRIUS 3RV2041-4YA15 motor protection circuit breaker, CLASS 10 trip, 100 kA at 240 V, screw-type terminals, snap-on DIN rail. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Note":"1","Depth":"176 mm","Solid":"2x (2.5 ... 16 mm²)","Width":"70 mm","title":"3RV2041-4YA15","Height":"165 mm","Upwards":"150 mm","at 24 V":"1 A","at 60 V":"0.15 A","at 230 V":"0.5 A","Downwards":"150 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S3 for motor protection, CLASS 10 A-release 75...93 A N-release 1300 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","Mounting Position":"any","Solid Or Stranded":"2x (2,5 ... 50 mm²), 1x (10 ... 70 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"20 hp","at 240 V rated value":"100 kA","at 400 V rated value":"30 kA","at 480 V rated value":"93 A","at 500 V rated value":"4 kA","at 600 V rated value":"93 A","at 690 V rated value":"3 kA","Design Of The Product":"For motor protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"7.5 hp","at 200/208 V rated value":"30 hp","at 220/230 V rated value":"40 hp","at 460/480 V rated value":"75 hp","at 575/600 V rated value":"100 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"65 kA","at AC at 500 V rated value":"8 kA","at AC at 690 V rated value":"5 kA","Size Of The Circuit-Breaker":"S3","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"25 000","at AC in hot operating state":"39 W","at AC-3 at 400 V rated value":"93 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"25 000","Substance Prohibitance (Date)":"03/01/2017","at AC-3e at 400 V rated value":"93 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"93 A","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","For Main Contacts For Ring Cable Lug":"4.5 ... 6 N·m","Surge Voltage Resistance Rated Value":"8 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"13 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 %","Finely Stranded Without Core End Processing":"2x (10 ... 35 mm²), 1x (10 ... 50 mm²)","For Main Contacts With Screw-Type Terminals":"4.5 ... 6 N·m","with high demand rate according to SN 31920":"50 %","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms Sinus","Electrical Endurance (Operating Cycles) Typical":"25 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S3","Outer Diameter Of The Usable Ring Cable Lug Maximum":"19 mm","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"1 300 A","insulation voltage with degree of pollution 3 at AC rated value":"1 000 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"75 ... 93 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7f7aca5ea19d99e6e6b7770a617768df.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629971&mlfb=3RV2041-4YA15"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3RV2041-4YA15?","answer":"The closest functional peer within the SIRIUS family is the 3RV2021-4NA25, which shares the same CLASS 10 trip class and screw-type terminal design, but differs in interrupting ratings and current range — verify the specific motor FLA and available fault current before substituting."},{"question":"What is the listed note (1) on the 3RV2041-4YA15?","answer":"The evidence lists a Note value of 1, but no further detail on what that note specifies is available in the current data."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2041-4YA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2041-4YA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}