{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2111-0FA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2111-0FA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2111-0FA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2111-0FA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2111-0FA10, motor protection circuit breaker with overload relay function, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw-type terminals, DIN rail mounting.","salesMarkdown":"## Motor protection circuit breaker, SIRIUS series Phase failure detection is included; ground fault detection is not built in. At 230 V rated value it handles 0.1 kW motor loads, so it is sized for smaller motors in conveyor, pump, or fan duty. Class 10 trip ensures the breaker disconnects before the motor winding overheats during a stall — the standard for standard-duty induction motors. The 15 operations per hour maximum at AC-3 duty governs repetitive starting; a furnace fan cycling more often needs a higher-rated device. The operating temperature range of -20 to +60 °C with temperature compensation allows deployment in unconditioned enclosures near furnaces or ovens, as long as the ambient stays within that span. Storage range extends to -50 to +80 °C. Any mounting position is permitted. Clearance requirements: 50 mm upwards and downwards, 0 mm forwards and backwards, 30 mm at the side — tight enough for dense panels. Dimensions are 97 mm deep, 65 mm wide, and 97 mm high. The M3 screw terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded conductors.","metaTitle":"Siemens 3RV2111-0FA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2111-0FA10 SIRIUS motor protection circuit breaker. Class 10 trip, phase failure detection, 100 kA breaking capacity at 400 V AC. Available to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"65 mm","title":"3RV2111-0FA10","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","Forwards":"0 mm","at 230 V":"1.5 A","at 690 V":"gL/gG 4 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for motor protection, CLASS 10 with overload relay function A-release 0.35...0.5 A N-release 6.5 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.5 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.5 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection with overload relay function","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.5 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","Design Of The Auxiliary Switch":"laterally","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.5 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C600 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 6 A, quick: 10 A","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"6.5 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.35 ... 0.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aa58222c62d39db88cb0cd3263293253.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=202984&mlfb=3RV2111-0FA10"},"ai":{"faq":[{"question":"Where can I buy 3RV2111-0FA10?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3RV2111-0FA10?","answer":"The rated breaking capacity is 100 kA at 400 V AC, and also 100 kA at 240 V, 500 V, and 690 V AC."},{"question":"What does Class 10 trip mean for this motor protection breaker?","answer":"Class 10 means the breaker trips within 10 seconds at a locked-rotor condition, protecting standard induction motors from overheating during a stall."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2111-0FA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2111-0FA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}