{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2111-0JA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2111-0JA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2111-0JA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2111-0JA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker for motor protection with overload relay function, 3RV2111-0JA10, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, screw-type terminals, 65 x 97 x 97 mm.","salesMarkdown":"Rated breaking capacity hits 100 kA at 400 V AC, 500 V, and 690 V — that is a genuine high-fault rating for a compact 65 mm wide device. Screw-type terminals for the main current circuit accept 2× (0.5…1.5 mm²) solid or stranded, or 2× (0.75…2.5 mm²) — sized for motor control wiring up to fractional horsepower. ## Mounting and integration — DIN rail, clearances, orientation Screw and snap-on fastening means you can pre-wire the breaker on the bench and clip it into the panel, or screw-mount it if the rail is full. Mounting position is any — horizontal, vertical, upside down — so it fits tight gland plates or vertical bus risers without derating. Clearance requirements: 50 mm upwards, 50 mm downwards, 30 mm at the side, zero forwards or backwards. The 97 mm depth and 65 mm width mean it occupies about the same footprint as a contactor of matching frame size — plan a 65 mm slot per motor branch on the DIN rail. That -20 °C floor is fine for most indoor panels but marginal for an unheated enclosure in a northern climate — if the panel sits below freezing at startup, the breaker will operate, but the motor current setting should be verified at ambient.","metaTitle":"Siemens 3RV2111-0JA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens SIRIUS 3RV2111-0JA10 motor protection circuit breaker. CLASS 10 trip, 100 kA breaking capacity at 400 V, screw terminals, phase failure detection. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"65 mm","title":"3RV2111-0JA10","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","Forwards":"0 mm","at 230 V":"1.5 A","at 500 V":"gL/gG 10 A","at 690 V":"gL/gG 10 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for motor protection, CLASS 10 with overload relay function A-release 0.7...1 A N-release 13 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.2 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"1 A","at 500 V rated value":"100 kA","at 600 V rated value":"1 A","at 690 V rated value":"100 kA","Design Of The Product":"For motor protection with overload relay function","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 575/600 V rated value":"0.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"1 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"1 A","Design Of The Auxiliary Switch":"laterally","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C600 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 6 A, quick: 10 A","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"13 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$52.07","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ae72bea28eb354bf3484a132866d8ebe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=48627&mlfb=3RV2111-0JA10"},"ai":{"faq":[{"question":"What is the 3RV2111-0JA10 used for?","answer":"It is a motor protection circuit breaker with integrated overload relay — one device for short-circuit and overload protection of a motor branch. The CLASS 10 trip is matched to standard induction motor starts, and the 100 kA breaking capacity at 400 V handles high-fault panels."},{"question":"Where can I buy the 3RV2111-0JA10?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here."},{"question":"Will the 3RV2111-0JA10 drop into a panel designed for the 3RV2011-0AA10?","answer":"Both are SIRIUS motor protection breakers on the same 65 mm wide DIN-rail footprint with screw terminals. The 3RV2111-0JA10 carries a higher 100 kA breaking capacity at 400 V versus the 3RV2011-0AA10's lower rating, so if the panel's available fault current exceeds the older breaker's rating, the 3RV2111-0JA10 is a direct-fit upgrade — same rail slot, same wiring method, no rewiring needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2111-0JA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2111-0JA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}