{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2111-1FA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2111-1FA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2111-1FA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2111-1FA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2111-1FA10 motor protection circuit breaker with integrated overload relay function, Trip Class 10, 100 kA breaking capacity at 400 V, screw-type terminals, 97 mm depth, 65 mm width.","salesMarkdown":"This means one device handles both short-circuit and overload protection for motor branch circuits, eliminating the need for a separate overload relay and contactor combination in many applications. The same 100 kA rating holds at 240 V and 500 V (cite:,). Panel integration is straightforward — the 65 mm width (cite:) fits standard enclosure cutouts, and the 97 mm depth (cite:) leaves clearance for wiring behind the device. Screw-type terminals on the main current circuit accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded wire (cite:,). Rated voltage range is 20 to 690 V. No ground fault detection. At 690 V the breaking capacity drops to 4 kA (cite:) — coordination with upstream fuses or breakers is essential for 690 V installations. The gL/gG fuse ratings at 400 V and 500 V are 32 A (cite:,), and 25 A at 690 V (cite:), defining the maximum backup fuse for the device. Mounting position is any (cite:), with minimum clearances of 50 mm upward and downward, 30 mm to the side, and 0 mm forward and backward (cite:,).","metaTitle":"Siemens 3RV2111-1FA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV2111-1FA10 SIRIUS motor protection circuit breaker, 100 kA breaking capacity at 400 V, Trip Class 10, 20-690 V rated range, DIN rail mount. Current production. Sourced t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"65 mm","title":"3RV2111-1FA10","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","Forwards":"0 mm","at 230 V":"1.5 A","at 400 V":"gL/gG 32 A","at 500 V":"gL/gG 32 A","at 690 V":"gL/gG 25 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for motor protection, CLASS 10 with overload relay function A-release 3.5...5 A N release 65 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"5 A","at 500 V rated value":"100 kA","at 600 V rated value":"5 A","at 690 V rated value":"4 kA","Design Of The Product":"For motor protection with overload relay function","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.17 hp","at 200/208 V rated value":"1 hp","at 220/230 V rated value":"1 hp","at 460/480 V rated value":"3 hp","at 575/600 V rated value":"3 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"5 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"5 A","Design Of The Auxiliary Switch":"laterally","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"5 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C600 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 6 A, quick: 10 A","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"65 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"3.5 ... 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2b1dbe9a03069870ae8e8c1c6f9b920b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=447384&mlfb=3RV2111-1FA10"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for 3RV2111-1FA10?","answer":"As a current-production SIRIUS device, Siemens provides CE declaration of conformity, UL/CSA certification documentation, and RoHS/REACH compliance declarations. These are available upon request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2111-1FA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2111-1FA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}