{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2311-0BC10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2311-0BC10","canonicalUrl":"https://aoctrl.com/siemens/3RV2311-0BC10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2311-0BC10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS S00 circuit breaker for starter combinations, 3RV2311-0BC10, 100 kA SCCR at 400 V AC, screw/snap-on 35 mm DIN rail, current production.","salesMarkdown":"## SIRIUS S00 circuit breaker for starter combinations It delivers 100 kA rated ultimate short-circuit breaking capacity (Icu) at 400 V AC — the same across 240 V, 500 V, and 690 V AC — so it clears a fault up to that level without cascading upstream, which is what you need when coordinating a motor branch circuit in a panel. Rated operational voltage spans 20 to 690 V, covering most low-voltage motor control schemes. The breaker is rated for AC-3 and AC-3e duty at a maximum of 15 switching operations per hour — that's the mechanical endurance for motor starting, not continuous load switching, so it fits a starter combination that cycles a few times per hour. Main circuit connections are screw-type terminals accepting 2x (0.75 to 2.5 mm²) solid/stranded or 2x 4 mm². The S00 frame size keeps the width at 45 mm, depth at 97 mm, height at 97 mm — fits a standard 45 mm-wide DIN slot with 50 mm clearance above and below, 30 mm to the side. ## Environmental and installation limits No ground-fault or phase-failure detection built in — those are handled upstream or by a separate module. The breaker is designed for starter combinations, meaning it integrates with a contactor and overload relay in a coordinated motor branch.","metaTitle":"Siemens 3RV2311-0BC10 SIRIUS Circuit Breaker, 100 kA SCCR","metaDescription":"Siemens 3RV2311-0BC10 SIRIUS S00 circuit breaker for starter combinations. 100 kA breaking capacity at 400 V AC. Screw/snap-on 35 mm DIN rail. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2311-0BC10","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for starter combination Rated current 0.2 A N-release 2.6 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.2 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.2 A","at 690 V rated value":"100 kA","Design Of The Product":"For starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.2 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.2 A","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.2 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"2.6 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f5c97d1ee0ed21403dfc82b5d8fe3f71.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=461951&mlfb=3RV2311-0BC10"},"ai":{"faq":[{"question":"Where can I buy the 3RV2311-0BC10?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of the 3RV2311-0BC10 at 400 V?","answer":"It delivers 100 kA rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, and the same 100 kA at 240 V, 500 V, and 690 V AC."},{"question":"What are the mounting dimensions for the 3RV2311-0BC10?","answer":"Width is 45 mm, depth 97 mm, height 97 mm. It mounts on 35 mm DIN rail per DIN EN 60715 with 50 mm clearance above and below, 30 mm to the side."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2311-0BC10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2311-0BC10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}