{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2311-0CC20","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2311-0CC20","canonicalUrl":"https://aoctrl.com/siemens/3RV2311-0CC20","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2311-0CC20","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, size S00, for starter combinations, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting onto 35 mm DIN rail, spring-loaded terminals.","salesMarkdown":"## SIRIUS S00 circuit breaker for starter combinations The Siemens 3RV2311-0CC20 is a SIRIUS-branded circuit breaker in size S00, designed specifically for starter combinations. Breaking capacity hits 100 kA at 240 V, 400 V, 500 V, and 690 V AC — that covers most industrial distribution panels without needing an upstream current-limiting fuse for fault levels up to that threshold. Rated operational voltage spans 20 to 690 V. Main contacts rated for 100,000 typical mechanical operations. Envelope is 97 mm deep, 45 mm wide, 106 mm tall. Clearance requirements: 50 mm upward, 50 mm downward, 30 mm to the side; zero forward or backward clearance needed. Any mounting position is permitted. Screwdriver shaft diameter 3 mm, tip size 3.0 x 0.5 mm.","metaTitle":"Siemens 3RV2311-0CC20 SIRIUS Circuit Breaker, S00, 100 kA","metaDescription":"Siemens 3RV2311-0CC20 SIRIUS circuit breaker, size S00, 100 kA breaking capacity at 400 V AC, screw/snap-on 35 mm DIN rail. Active lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","Mounting Position":"any","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.25 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.25 A","at 690 V rated value":"100 kA","Design Of The Product":"For starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"spring-loaded terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.25 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.25 A","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.25 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (20 ... 12)","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"3.3 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=417612&mlfb=3RV2311-0CC20","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2311-0CC20/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2311-0CC20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2311-0CC20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}