{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2311-0DC10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2311-0DC10","canonicalUrl":"https://aoctrl.com/siemens/3RV2311-0DC10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2311-0DC10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2311-0DC10 circuit breaker for starter combinations, Size S00, 45 mm width, 97 mm depth, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"## What this breaker carries — and what it doesn't The 100 kA breaking capacity at 400 V and at 690 V tells you it can sit on a high-fault panel bus without cascading upstream, but the 0 kW rating at 230 V and 0.32 A at 480 V and 600 V are the actual motor-protection trip settings — this is a low-current thermal-magnetic breaker for fractional-horsepower or small-pump loads, not a 100 A feeder. ## DIN-rail fit and panel clearance That means you can pack it tight front-to-back in a shallow enclosure, but need breathing room above and below for arc-chamber venting and wiring access. ## What the 100 kA rating means for coordination The 100 kA breaking capacity at 240 V, 400 V, 500 V, and 690 V AC means this breaker can interrupt a fault up to 100,000 amps without welding or rupturing — that's a high-fault rating for a Size S00 frame. The 0.32 A trip at 480 V and 600 V is the actual overload setting — the 100 kA is the short-circuit withstand, not the running current.","metaTitle":"Siemens 3RV2311-0DC10 SIRIUS Circuit Breaker, Size S00, 100","metaDescription":"Siemens 3RV2311-0DC10 SIRIUS circuit breaker for starter combinations. Size S00, 45 mm wide, 100 kA breaking capacity at 400 V. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.32 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.32 A","at 690 V rated value":"100 kA","Design Of The Product":"For starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.32 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.32 A","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.32 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"4.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/708a19328118dc533aee598514525749.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=247486&mlfb=3RV2311-0DC10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2311-0DC10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV2311-0DC10 and get current pricing?","answer":"The 3RV2311-0DC10 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price figure is published here."},{"question":"What is 3RV2311-0DC10's width and depth for panel layout?","answer":"The width is 45 mm and the depth is 97 mm, both standard for the S00 frame size. Clearance needed: 50 mm above and below, 30 mm to the sides."},{"question":"Will 3RV2311-0DC10 drop into a panel specified for 3RV2011-0AA10?","answer":"Both are Size S00 breakers on 35 mm DIN rail with the same 45 mm width and 97 mm depth footprint, so the mechanical fit is identical. The electrical ratings differ — verify the trip settings match your motor load before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2311-0DC10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2311-0DC10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}