{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2311-1GC10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2311-1GC10","canonicalUrl":"https://aoctrl.com/siemens/3RV2311-1GC10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2311-1GC10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2311-1GC10 circuit breaker for starter combinations, 45 mm width, 100 kA breaking capacity at 400 V, screw-type terminals, DIN rail mount.","salesMarkdown":"The screw-type terminals on the main circuit accept 2x 0.75 to 2.5 mm² solid or stranded wire, or 2x 4 mm². Breaking capacity is the headline here: 100 kA at 240 V, 400 V, and 500 V, dropping to 4 kA at 690 V. The gL/gG fuse-limit ratings (50 A at 400 V, 40 A at 500 V, 35 A at 690 V) tell you the maximum upstream fuse that still lets the breaker coordinate properly. ## Panel fit and clearances Footprint is 45 mm wide by 97 mm deep by 97 mm tall — a standard 45 mm module width that matches most SIRIUS contactor and overload relay companions. Clearance requirements: 50 mm upwards and downwards, 30 mm to the side, zero forwards and backwards. That zero forward clearance means you can butt it against a panel door or another device without derating, as long as the side and vertical gaps are respected.","metaTitle":"Siemens 3RV2311-1GC10 SIRIUS Circuit Breaker, 100 kA at 400","metaDescription":"Siemens 3RV2311-1GC10 SIRIUS circuit breaker for starter combinations. 100 kA breaking capacity at 400 V, 45 mm wide, DIN rail mount. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 400 V":"gL/gG 50 A","at 500 V":"gL/gG 40 A","at 690 V":"gL/gG 35 A","Backwards":"0 mm","Downwards":"50 mm","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"6.3 A","at 500 V rated value":"100 kA","at 600 V rated value":"6.3 A","at 690 V rated value":"4 kA","Design Of The Product":"For starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.25 hp","at 200/208 V rated value":"1 hp","at 220/230 V rated value":"1.5 hp","at 460/480 V rated value":"3 hp","at 575/600 V rated value":"5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"6.3 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"6.3 A","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"6.3 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"82 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$34.29","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6df1bf7cee055077cc176f0f46da9ca2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1140&mlfb=3RV2311-1GC10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2311-1GC10/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV2311-1GC10 at 400 V?","answer":"100 kA at 400 V rated value, which is the same at 240 V and 500 V. At 690 V it drops to 4 kA."},{"question":"Will 3RV2311-1GC10 drop into a panel specified around 3RV2021-1GA15 without rewiring?","answer":"Both are 45 mm wide SIRIUS circuit breakers with screw-type terminals on DIN rail, so the mechanical fit and terminal type are the same. However, the 3RV2311-1GC10 is designed for starter combinations, while the 3RV2021-1GA15 is a standard motor-protective circuit breaker — verify the auxiliary contact configuration and the specific coordination class (Type 1 vs Type 2) for your starter assembly before swapping."},{"question":"Where can I buy 3RV2311-1GC10 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time, no stock or price figures published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2311-1GC10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2311-1GC10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}