{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2321-4DC10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2321-4DC10","canonicalUrl":"https://aoctrl.com/siemens/3RV2321-4DC10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2321-4DC10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker 3RV2321-4DC10, 45 mm width, for starter combinations, 100 kA breaking capacity at 240 V AC, screw-type terminals, DIN rail mount.","salesMarkdown":"Rated voltage spans 20 to 690 V, covering most low-voltage motor circuits globally. At 400 V the breaking capacity is 25 kA, at 500 V it drops to 5 kA, and at 690 V to 2 kA — so the SCCR headroom shrinks as line voltage rises; verify your point-of-fault current at the actual system voltage. The motor horsepower ratings are given for several common voltages: 3 hp at 230 V, 7.5 hp at 220/230 V, 15 hp at 460/480 V. This tells you the maximum motor frame it can protect at those voltages — not the continuous current rating alone, but the motor full-load current the breaker is calibrated to coordinate with. The switching frequency is limited to 15 operations per hour at AC-3 and AC-3e duty — that is about one start every four minutes, so it is sized for infrequent starting (pumps, fans, compressors) rather than jogging or high-cycle applications. Fuse backup ratings are specified: at 400 V use a gL/gG 63 A fuse upstream, at 500 V and 690 V use gL/gG 50 A. These are the maximum fuse sizes that preserve the breaker's interrupting rating — if you fuse higher, the breaker may not clear a fault safely. The conductor cross-section accepted is 2x 1 to 2.5 mm² or 2x 2.5 to 10 mm² solid or stranded, with M4 screws on the main contacts. ## Physical fit and clearance needs Dimensions are 45 mm width, 97 mm height, 97 mm depth. The 45 mm width is three standard 15 mm module spaces on DIN rail — important for panel fill calculations. Clearance requirements: 50 mm upwards, 50 mm downwards, 30 mm at the side, 0 mm forwards and backwards. The zero forward/backward clearance means it can be mounted flush against a panel door or backplate without derating, but the 50 mm vertical gap above and below must be kept free for arc venting and heat dissipation.","metaTitle":"Siemens 3RV2321-4DC10 SIRIUS Circuit Breaker, 45 mm, 100 kA","metaDescription":"Siemens 3RV2321-4DC10 SIRIUS circuit breaker for starter combinations. 45 mm width, 100 kA breaking capacity at 240 V AC. DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ae0ce82cd63105b5f4208ef453e1c7bb.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=501716&mlfb=3RV2321-4DC10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2321-4DC10/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2321-4DC10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2321-4DC10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}