{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2331-4XC10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2331-4XC10","canonicalUrl":"https://aoctrl.com/siemens/3RV2331-4XC10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2331-4XC10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2331-4XC10 circuit breaker for starter combinations, 59 A rated current at 480/600 V, 30 kA breaking capacity at 400 V, screw-type terminals, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"Rated 59 A at both 480 V and 600 V, with a breaking capacity of 30 kA at 400 V and 100 kA at 240 V. That 30 kA at 400 V means it can safely interrupt a fault current up to 30,000 A on a 400 V line — enough headroom for most industrial distribution panels without needing an upstream current-limiting fuse. ## Panel fit and clearances Dimensions: 149 mm deep, 55 mm wide, 140 mm tall. The 55 mm width is a three-module footprint on the DIN rail — common for this class of motor-protective breaker. At 400 V, the upward clearance must be 160 mm for arc flash containment; at 500 V it's 125 mm, at 690 V it's 100 mm. At 240 V no clearance is required. Plan the gland plate and busbar routing accordingly. Terminals accept 2x (1 to 35 mm²) or 1x (1 to 50 mm²) solid or stranded copper — M6 main contact screws. ## Operating conditions and ratings Rated operating voltage range 20 to 690 V. No ground fault detection, no phase failure detection built in — this is a straight thermal-magnetic or electronic motor-protective breaker; external monitoring is needed if those functions are required.","metaTitle":"Siemens 3RV2331-4XC10 SIRIUS Circuit Breaker, 59 A, 30 kA at","metaDescription":"Siemens SIRIUS 3RV2331-4XC10 circuit breaker for starter combinations. 59 A rated current, 30 kA breaking capacity at 400 V. Screw/snap-on 35 mm DIN rail. Current production. Avail","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"149 mm","Width":"55 mm","Height":"140 mm","Upwards":"50 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"160","at 500 V":"125","at 690 V":"100","Backwards":"0 mm","Downwards":"50 mm","At The Side":"10 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M6","Mounting Position":"any","Solid Or Stranded":"2x (1 ... 35 mm²), 1x (1 ... 50 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"10 hp","at 240 V rated value":"100 kA","at 400 V rated value":"30 kA","at 480 V rated value":"59 A","at 500 V rated value":"4 kA","at 600 V rated value":"59 A","at 690 V rated value":"2 kA","Design Of The Product":"For starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"5 hp","at 220/230 V rated value":"20 hp","at 460/480 V rated value":"40 hp","at 575/600 V rated value":"50 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"65 kA","at AC at 500 V rated value":"8 kA","at AC at 690 V rated value":"4 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S2","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"20 000","at AC in hot operating state":"26 W","at AC-3 at 400 V rated value":"59 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"20 000","Substance Prohibitance (Date)":"03/01/2017","at AC-3e at 400 V rated value":"59 A","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"59 A","at AWG cables for main contacts":"2x (18 ... 2), 1x (18 ... 1)","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"8.7 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (1 ... 25 mm²), 1x (1 ... 35 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"3 ... 4.5 N·m","with high demand rate according to SN 31920":"50 %","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms Sinus","Electrical Endurance (Operating Cycles) Typical":"20 000","Size Of Contactor Can Be Combined Company-Specific":"S2","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"845 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ed5025819ce578174f292a93e0bfb324.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=219003&mlfb=3RV2331-4XC10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2331-4XC10/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2331-4XC10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2331-4XC10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}