{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2332-4DC10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2332-4DC10","canonicalUrl":"https://aoctrl.com/siemens/3RV2332-4DC10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2332-4DC10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV2332-4DC10, for starter combinations, 50 kA breaking capacity at 400 V AC, screw terminals, 55 x 140 x 149 mm.","salesMarkdown":"At 690 V the rated short-circuit breaking capacity is 5 kA, and at 240 V it reaches 100 kA, so the part's real-world interrupting rating depends on which line voltage your installation uses. ## Sizing for motor loads This breaker carries motor horsepower ratings across common North American and IEC voltage bands: 5 hp at 230 V, 10 hp at 220/230 V, 20 hp at 460/480 V, and 7.5 hp at 200/208 V. Those ratings tell you the maximum induction motor it can protect at those voltages — useful when filling a BOM line for a pump or conveyor drive section. Main circuit connections are screw-type terminals accepting 2x (1 to 35 mm²) or 1x (1 to 50 mm²) solid or stranded copper — M6 stud size on the main contacts.","metaTitle":"Siemens 3RV2332-4DC10 SIRIUS Circuit Breaker, 50 kA at 400 V","metaDescription":"Siemens 3RV2332-4DC10 SIRIUS circuit breaker for starter combinations. Rated 50 kA breaking capacity at 400 V. Current lifecycle stage. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"149 mm","Width":"55 mm","Height":"140 mm","Upwards":"50 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"100","at 500 V":"80","at 690 V":"63","Backwards":"0 mm","Downwards":"50 mm","At The Side":"10 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M6","Mounting Position":"any","Solid Or Stranded":"2x (1 ... 35 mm²), 1x (1 ... 50 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"50 kA","at 480 V rated value":"25 A","at 500 V rated value":"10 kA","at 600 V rated value":"25 A","at 690 V rated value":"5 kA","Design Of The Product":"For starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"2 hp","at 200/208 V rated value":"7.5 hp","at 220/230 V rated value":"10 hp","at 460/480 V rated value":"20 hp","at 575/600 V rated value":"25 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"18 kA","at AC at 690 V rated value":"8 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S2","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"50 000","at AC in hot operating state":"14.5 W","at AC-3 at 400 V rated value":"25 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"50 000","Substance Prohibitance (Date)":"10/15/2014","at AC-3e at 400 V rated value":"25 A","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"25 A","at AWG cables for main contacts":"2x (18 ... 2), 1x (18 ... 1)","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"4.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (1 ... 25 mm²), 1x (1 ... 35 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"3 ... 4.5 N·m","with high demand rate according to SN 31920":"50 %","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms Sinus","Electrical Endurance (Switching Cycles) Typical":"50 000","Size Of Contactor Can Be Combined Company-Specific":"S2","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"325 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f8d8832192b082317cdb48a0ccbd305e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=341479&mlfb=3RV2332-4DC10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2332-4DC10/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2332-4DC10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2332-4DC10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}