{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2332-4RC10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2332-4RC10","canonicalUrl":"https://aoctrl.com/siemens/3RV2332-4RC10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2332-4RC10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2332-4RC10 circuit breaker for starter combinations, 55 mm wide, 50 kA breaking capacity at 400 V AC, screw-type terminals, DIN rail mount.","salesMarkdown":"Rated for operating voltages from 20 to 690 V AC, it delivers a breaking capacity of 50 kA at 400 V, 100 kA at 240 V, 8 kA at 500 V, and 4 kA at 690 V — so the interrupting capability scales with the line voltage you're working on. Motor power ratings are given per common North American and European voltage standards: 60 hp at 460/480 V, 75 hp at 575/600 V, 30 hp at 220/230 V, and 22 kW at 230 V. At 55 mm wide, 140 mm tall, and 149 mm deep, it takes up a standard three-module footprint on the rail — plan your enclosure backpanel layout accordingly. That 50 mm top/bottom gap matters for airflow and for routing the M6 main-circuit terminals. Terminals accept 2x 1–35 mm² or 1x 1–50 mm² solid or stranded copper — plenty of cross-section for the 77 A continuous rating at 480/600 V. No ground-fault or phase-failure detection built in — those are handled separately upstream or in the motor starter assembly.","metaTitle":"Siemens 3RV2332-4RC10 SIRIUS Circuit Breaker, 55 mm, 50 kA a","metaDescription":"Siemens 3RV2332-4RC10 SIRIUS circuit breaker for starter combinations. 55 mm wide, 50 kA breaking capacity at 400 V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"149 mm","Width":"55 mm","Height":"140 mm","Upwards":"50 mm","Forwards":"0 mm","at 240 V":"none required","at 400 V":"160","at 500 V":"125","at 690 V":"100","Backwards":"0 mm","Downwards":"50 mm","At The Side":"10 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"M6","Mounting Position":"any","Solid Or Stranded":"2x (1 ... 35 mm²), 1x (1 ... 50 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"22 kW","at 240 V rated value":"100 kA","at 400 V rated value":"50 kA","at 480 V rated value":"77 A","at 500 V rated value":"8 kA","at 600 V rated value":"77 A","at 690 V rated value":"4 kA","Design Of The Product":"For starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"7.5 hp","at 200/208 V rated value":"25 hp","at 220/230 V rated value":"30 hp","at 460/480 V rated value":"60 hp","at 575/600 V rated value":"75 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"10 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S2","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"20 000","at AC in hot operating state":"29.5 W","at AC-3 at 400 V rated value":"80 A","Of Auxiliary Contacts Typical":"20 000","Substance Prohibitance (Date)":"03/01/2017","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"80 A","at AWG cables for main contacts":"2x (18 ... 2), 1x (18 ... 1)","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"9.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (1 ... 25 mm²), 1x (1 ... 35 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"3 ... 4.5 N·m","with high demand rate according to SN 31920":"50 %","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms Sinus","Electrical Endurance (Operating Cycles) Typical":"20 000","Size Of Contactor Can Be Combined Company-Specific":"S2","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"1 040 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bdfc310932af3498acf1137ba2121149.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=365680&mlfb=3RV2332-4RC10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2332-4RC10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV2332-4RC10 and how do I get a price?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ through the storefront."},{"question":"What are the key ratings for 3RV2332-4RC10?","answer":"Breaking capacity: 50 kA at 400 V AC, 100 kA at 240 V, 8 kA at 500 V, 4 kA at 690 V. Motor power: 60 hp at 460/480 V, 75 hp at 575/600 V, 22 kW at 230 V. Width: 55 mm. Mounts on 35 mm DIN rail."},{"question":"Will 3RV2332-4RC10 drop into a panel built for 3RV2011-0AA10?","answer":"No — the 3RV2332-4RC10 is 55 mm wide versus the 45 mm width of the 3RV2011 series, and the terminal layout differs. Expect to rework the DIN rail and wiring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2332-4RC10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2332-4RC10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}