{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2341-4HC10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2341-4HC10","canonicalUrl":"https://aoctrl.com/siemens/3RV2341-4HC10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2341-4HC10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2341-4HC10 circuit breaker for starter combinations, screw and snap-on mounting onto 35 mm DIN rail, 30 kA at 400 V AC, active lifecycle.","salesMarkdown":"The 65 kA at 400 V AC applies under a different test condition (likely higher prospective current or a specific upstream fuse/breaker pairing), so the 30 kA is the conservative figure for general duty. Any mounting position is acceptable. Clearance requirements: 150 mm upward and downward, 30 mm at the sides, zero forward or backward — so plan for vertical breathing space but no extra depth behind the rail. ## Termination and conductor sizing Main circuit terminals are screw-type. Accepts solid or stranded conductors: 2x (2.5... 16 mm²) for the smaller pair, and for the larger connection 2x (2.5... 50 mm²) or 1x (10... 70 mm²). That covers everything from control-circuit wiring up to a 70 mm² main feeder — no need for lug adapters on typical motor branch circuits up to about 50 A. ## Environmental and operating limits The storage limit is wider because it governs handling, not running — fine for warehouse or trucking. Rated voltage span is 20... 690 V, covering most low-voltage three-phase systems globally.","metaTitle":"Siemens 3RV2341-4HC10 SIRIUS Circuit Breaker, 30 kA at 400 V","metaDescription":"Siemens 3RV2341-4HC10 SIRIUS circuit breaker for starter combinations. Rated 30 kA at 400 V AC. Screw and snap-on DIN rail mount. Active production. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"176 mm","Solid":"2x (2.5 ... 16 mm²)","Width":"70 mm","Height":"165 mm","Upwards":"150 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"150 mm","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","Mounting Position":"any","Solid Or Stranded":"2x (2,5 ... 50 mm²), 1x (10 ... 70 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"10 hp","at 240 V rated value":"100 kA","at 400 V rated value":"30 kA","at 480 V rated value":"50 A","at 500 V rated value":"6 kA","at 600 V rated value":"50 A","at 690 V rated value":"3 kA","Design Of The Product":"For starter combinations","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"5 hp","at 200/208 V rated value":"15 hp","at 220/230 V rated value":"20 hp","at 460/480 V rated value":"40 hp","at 575/600 V rated value":"50 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"65 kA","at AC at 500 V rated value":"12 kA","at AC at 690 V rated value":"6 kA","Size Of The Circuit-Breaker":"S3","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"25 000","at AC in hot operating state":"27 W","at AC-3 at 400 V rated value":"50 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"25 000","Substance Prohibitance (Date)":"03/01/2017","at AC-3e at 400 V rated value":"50 A","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"50 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","For Main Contacts For Ring Cable Lug":"4.5 ... 6 N·m","Surge Voltage Resistance Rated Value":"8 kV","at AC in hot operating state per pole":"9 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (2.5 ... 35 mm²), 1x (2.5 ... 50 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 %","Finely Stranded Without Core End Processing":"2x (10 ... 35 mm²), 1x (10 ... 50 mm²)","For Main Contacts With Screw-Type Terminals":"4.5 ... 6 N·m","with high demand rate according to SN 31920":"50 %","shock resistance according to IEC 60068-2-27":"25g / 11 ms Sinus","Electrical Endurance (Operating Cycles) Typical":"25 000","Size Of Contactor Can Be Combined Company-Specific":"S3","Outer Diameter Of The Usable Ring Cable Lug Maximum":"19 mm","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"650 A","insulation voltage with degree of pollution 3 at AC rated value":"1 000 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a091c91cf86dd12c4c9900ed835f0c70.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629994&mlfb=3RV2341-4HC10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2341-4HC10/alternatives.json"},"ai":{"faq":[{"question":"What DIN rail does 3RV2341-4HC10 mount on?","answer":"Screw and snap-on mounting onto 35 mm DIN rail per DIN EN 60715. Any mounting position is permitted."},{"question":"What conductor sizes does 3RV2341-4HC10 accept?","answer":"Screw terminals accept 2x (2.5... 16 mm²) solid/stranded for the smaller connection, and 2x (2.5... 50 mm²) or 1x (10... 70 mm²) for the larger main circuit connection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2341-4HC10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2341-4HC10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}